Andivi TRC-d Technisch handboek - Pagina 5

Blader online of download pdf Technisch handboek voor {categorie_naam} Andivi TRC-d. Andivi TRC-d 19 pagina's.

Andivi TRC-d Technisch handboek
Andivi – TRC-D – Technical Manual

INSTALLATION

MOUNTING ON ELECTRIC BOX
1. Separate the back plate from the controller by loosening the cover screw.
2. Align the mounting holes on the screw holes of the electric box. Suitable is a 3-module electric box 3M, for example Gewiss
GW24203, GW24207; TEM Catez DM30, HM30. The electric box is mounted vertically.
3. Fix the back plate on the electric box by tightening the back plate screws. Suggested for use is Philips wider "truss head"
or "washer head" #6-32x 3/4"(20mm).
4. DO NOT let the bolt head rise above the wall of the mounting holes of the back plate. It might cause a short circuit of the
room controller.
MOUNTING FRONT COVER
1. Lock front cover on the back plate by tightening the cover screw underneath with screwdriver of Philips electronic instrument
type or similar.
WIRING EXAMPLE
All wires that come from electric box must be inserted above the retainers of respective terminal block before tightening the
captive screws.
Fig. 2-1:
2-Pipe Control, 230VAC
Fig. 2-2:
4-Pipe Control, 230VAC
5
08/14, fw. ver. V1.2, V1.3
1
2
Cooling/Heating valve
3
4
5
I.
6
II.
7
Fan
III.
8
RS
9
Remote sensor (RS)
COM
10
Protect mode input (PROT)
ESI
11
C+
12
C -
13
Economy mode input (ECON)
ESI2
14
15
16
Cooling valve
Heating valve
I.
II.
FAN
III.
Remote sensor (RS)
Protect mode input (PROT)
Economy mode input (ECON)
N L
Modbus
N L
Modbus