Dispensing Hoses and Nozzles

9.
The unit may or may not be supplied with dispensing hose and nozzle assemblies.
If customer supplied hose assemblies, pylons, reels, safe breaks and nozzles are used they must
comply with the requirements outlined in AS/NZS 222.

Breakaways

9.1
For all dispensers fitted with breakaways, ensure the breakaway is installed between the nozzle
and the high-mast or pylon (if fitted). Any breakaways that have been subject to a break-away
situation should be inspected and refitted or replaced in accordance with the original
manufacturer's instructions.

Setting up the C4000

10.
Once the pump is connected on site, the final setup check and calibration to complete the
installation must be carried out, using the Parameter Switch and Calibration (K-Factor) Switch.
These switches are found on the C4000 Microprocessor Board which is housed in a metal
enclosure located behind one of the inner column panels.

Configuration Code

10.1
The configuration code has been set at Compac and should not be changed
In the event of it being lost and having to be re-entered the configuration is written on the yellow
label on the C4000 processor board cover.

Submersible Delay (Sd)

10.2
This is the time delay from when the Submersible pump starts to when the solenoids in the
dispenser open to allow time for the leak detector to reset.
This is factory set by Compac at 005 (five seconds).
If problems are experienced with the leak detector tripping, firstly check that 'Sd' is still set and
then, if necessary, make it longer as follows.
1. Press and release the K factor switch repeatedly until 'Sd' appears on the Dollar display
'dXXX' will appear in the litres display.
2. Continue to press the K factor switch until the number to be changed flashes. Hold the switch
down and this number will then increment.
3. Release the switch when the required number is displayed. The value of the displayed number
will then be stored in the C4000 memory as the Submersible Delay.

Parameter Switch Settings

10.3
10.3.1
Setting the Pump Number
This must be set at the pump, for each hose, so that communications with
a controller can take place. The location of this switch is shown in the
diagram below.
Depress the Parameter Switch nine (9) or more times until the message
'PnA XX' appears in the litres display window. When the switch is
pressed again 'Pnb XX ' will appear on the display. These two options
will toggle each time the switch is pressed. To alter either of the pump numbers, press and hold
the Parameter Switch when the pump number to be altered appears on the display. This number
will then increment. The switch should be released when the desired pump number is displayed.
The value of the displayed number will then be stored in the C4000 memory as the pump
number for that hose.
NOTE: For a single hose only 'Pn" will appear
\\Cilaklfs1\shrdata\Masters\Installation Sheets\Laser\L160SD Installation Sheet.doc