Electrolux DD 8795 Gebruikershandleiding - Pagina 4

Blader online of download pdf Gebruikershandleiding voor {categorie_naam} Electrolux DD 8795. Electrolux DD 8795 20 pagina's.

For the installer

• When used as an extractor unit, the hood must be fitted with a
150mm diameter duct.
• When installing the hood observe the following minimum
distances from the cooking top:
Electric cooking hobs
• The national Standard on fuel-burning systems specifies a maximum
depression of 0.04 mbar in such rooms.
• The air outlet must not be connected to chimney flues or combustion
gas ducts. The air outlet must under no circumstances be connected
to ventilation ducts for rooms in which fuel-burning appliances are
installed.
• The air outlet installation must comply with the regulations laid down
by the relevant authorities.
• When the unit is used in its extractor version, a sufficiently large
ventilation hole must be provided, with dimensions that are approxi-
mately the same as the outlet hole.
• National and regional building regulations impose a number of
restrictions on using hoods and fuel-burning appliances connected
to a chimney, such as coal or oil room-heaters and gas fires, in the
same room.
• Hoods can only be used safely with appliances connected to a
chimney if the room and/or flat (air/environment combination) is
ventilated from outside using a suitable ventilation hole approxi-
mately 500-600 cm
being created during operation of the hood.
• If you have any doubts, contact the relevant controlling authority or
building inspector's office.
• Since the rule for rooms with fuel burning appliances is "outlet hole
of the same size as the ventilation hole", a hole of 500-600 cm
which is to say a larger hole, could reduce the performance of the
extractor hood.
• If the hood is used in its filtering function, it will operate simply and
safely in the above conditions without the need for any of the
aforementioned measures.
• When the hood is used in its extractor function, the following rules
must be followed to obtain optimal operation:
- short and straight outlet ducting
- keep bends in outlet ducting to a minimum
- never install the ducts with an acute angle, they must always follow
a gentle curve.
- keep the duct as large as possible (preferably the same diameter
4
300mm.
large to avoid the possibility of a depression
2
,
2