OPTIONAL ACCESSORIES CONT.
3.
* Promate
Elapsed Time Indicator: A non-resettable display of the operating hours. Useful for scheduling and recording
TM
maintenance and lamp replacement.
4. * Promate
Integral Key Lock Switch: Ensures tamperproof operation, in either the "ON" or "OFF" position.
TM
5. Promate
Disposable Filters: Cardboard frame filters, for use when frequent filter changes are necessary.
TM
6. Promate
Ceiling Mount Kit: Kit includes four (4) eyebolts to suspend sanitizer from the ceiling.
TM
Wall Mounting Kit: Designed to allow unit to mount to a vertical wall in a horizontal position.
7.
Promate
TM
8.
Zenith™ UV-C Detector: A sensitive, hand-held, self-contained battery operated ultraviolet meter that can be used for:
• Monitoring UV-C Germicidal Lamp Intensity & Aging
• Measuring UV-C Germicidal Fixture Leakage
9.
Promate
Safety Glasses: Safety eyewear MUST be used as general-purpose safety protection and for additional shielding
TM
from ultraviolet rays.
10. Promate
Face Shield: Lightweight visor with adjustable headgear provides eye and face protection from germicidal
TM
ultraviolet rays.
* This accessory must be ordered at the time of initial equipment purchase. All other accessories can be ordered and installed at
the time of initial equipment purchase and installation or added at a later date.
For more information and purchasing contact our offices, weekdays between 8:30 am and 5:00 pm Eastern time, at: Atlantic
Ultraviolet Corporation
, 375 Marcus Boulevard, Hauppauge, New York, 11788
®
Tel: 631.273.0500 • Fax: 631.273.0771 • Email: [email protected] • Website: Ultraviolet.com – BuyUltraviolet.com
TROUBLESHOOTING
Always disconnect power to the fixture before performing any service or maintenance.
and ultraviolet resistant face shield, if troubleshooting SANITAIRE
IMPORTANT: This unit is to be serviced ONLY by qualified, and appropriately trained and/or licensed personnel.
Problem
SANITAIRE
®
unit
not operating.
Internal blower(s) not
functioning.
(1) STER-L-RAY
®
Germicidal
Lamp not operating
All STER-L-RAY
®
Germicidal
Lamps not operating.
If the above measures fail to correct the problem(s), contact our UV Application Specialists. Contact options can be found in
the "User Assistance" section.
Use personal protection equipment, such long sleeves with no gaps between cuffs and gloves,
Table 1 – Troubleshooting
Possible Cause
No electrical power.
Power connection to fixture is loose or disconnected.
Loose power connection.
Faulty blower motor.
Surelite
™
Ballast not functioning.
STER-L-RAY
®
Germicidal lamp not operating.
®
STER-L-RAY
Germicidal lamp not properly seated.
Surelite
™
Ballast not functioning.
STER-L-RAY
®
Lamps not installed.
Interlock switch open.
Interlock switch faulty.
.
®
Corrective Action
Verify that the unit is connected to a live
power source.
Verify power connection to fixture is
fully engaged.
Confirm connection to blower; connection is
tight and makes full contact.
Replace blower motor.
Swap lamp, with known good lamp. If good
lamp still does not operate, replace ballast.
Swap suspect lamp, with known good lamp. If
suspect lamp still does not operate, replace lamp.
Confirm contact of lamp and lampholder is
tight and lampholder is making full contact
with lamp.
Locate corresponding ballast and replace.
Install lamps.
Confirm access cover is on and latched.
Replace interlock switch.
11