Safety and Regulatory Compliance
The DS 16S and DS 16SE have passed extensive testing and comply with the following specifications and uses:
LISTED to ANSI/UL 1480-2005
• Fire Protective Signaling Use – UL Category UUMW, File Number S 3241.
Control Number 42S9 when installed with a junction box (on-wall or in-wall)
Not for use with DC-supervised systems.
• General Purpose Use – UL Category UEAY, File Number S 5591 Control Number 3N89.
• The DS 16SE is suitable for use outdoors in wet locations.
• The DS 16S is suitable for use indoors in damp locations.
• Suitable for installation using Class 1, Class 2, or Class 3 wiring methods in accordance with NFPA 70, National Electric
Code, 2002, Article 640.
• Suitable for use with fire alarm circuit wiring methods in accordance with NFPA 70, National Electric Code, 2002, Article
760.
• EMC Directive 89/336/EEC and Article 10 (1) of the directive, EN50081-1 and EN50082-1 as signified by the CE mark.
The DS 16S and DS 16SE also have been designed to the requirements defined in the following European regulatory
specification for combination systems:
• British Standard Code of Practice BS 5839, Part 8.
• Tested to IEC60268-5.
UL Sensitivity Wattage Tap Sound Pressure Level dBA at 3.1 meters (10 feet):
Wattage
ANSI/UL 1480-2005
Tap
70V
1 Watt
73 dBA
2 Watt
75 dBA
4 Watt
78 dBA
8 Watt
81 dBA
16 Watt
83 dBA
8 Ohm
83 dBA
SPLs given are per the UL 1480 specified reporting method.
Frequency response:
Fire alarm: 400 Hz to 4 kHz
General signaling: 80 Hz to 16 kHz (±3dB)
The Declaration of Conformity for this product
can be found at
www.bose.com/static/compliance/index.html.
Wire gauge
®
The FreeSpace
DS 16S and DS 16SE loudspeaker brackets are designed to work with 18 AWG (0.8 mm
to 14 AWG (2.0 mm
2
) size wire only.
100V
–
75 dBA
78 dBA
81 dBA
83 dBA
83 dBA
Installation
2
)
11