SYNCHRONIZING SYSTEM FUNCTIONS (cont.)
Device
Number
Function
Controls (cont.)
Speed Control
Speed matching range
of operation
Time Between Jogs
Jog Duration
Kicker Pulse Rate
Kicker Pulse Duration
Voltage Control
Voltage matching range
of operation
Time Between Jogs
Jog Duration
(3) A 1 to 15 second range is available.
(4) Proportional to error. Proportional Jog Duration is 1 to 10 seconds per Hz of frequency mismatch, linear
r
for
F (delta frequency) of 0.015 to 1.5 Hz of mismatch.
(5) One pulse per 6 to 120 seconds. A generator raise speed jog is produced in the time set on the Kicker
Pulse Duration Dial if the speed matcher does not operate.
(6) A 2 to 30 second range is available.
(7) Proportional to error. Proportional Jog Duration is 0.1 to 1.0 second per volt of mismatch, linear for
(delta voltage) of 1 to 20 V of mismatch.
Nominal Settings
Nominal Voltage
Nominal Current
VT Configuration Line-Line
Seal-in Delay
* Maximum measured range for (25) function settings is < 600 V.
Setpoint
Ranges
30 to 85 Hz
2 to 30 seconds
(4)
(5)
0.1 to 1.5 seconds
30 to 200 V ac
1 to 15 seconds
(7)
50 to 500 V*
0.50 to 6.00 A
(For 25 Function)
2 to 8160 Cycles
–5–
M‑5625 Digital Synchronizing System
Increment
—
—
(3)
—
—
—
—
(6)
—
—
1 V
0.01 A
1 Cycle
Accuracy
—
±20% of setting
±20% of setting
±20% of setting
±20% of setting
—
±20% of setting
±20% of setting
r
V
—
—
1 Cycle or 1%