Communicator Installation Configuration

EN50131-1 Installation Requirements
For EN50131-1 compliant installations, the following programming options shall be set as described.
Supervision Heartbeat (required for ATS4 and ATS5):
• [851][004] set to 0087h (135s heartbeat).
NOTE: The compatible receiver at ARC location shall have supervision window programmed for
1800s (ATS4) or 180s (ATS 5).
• [851][005] options 1 and 3 shall be enabled
Test transmission (required for ATS3):
• [851] System test options [026] and [027] shall be enabled (FF) for the communication paths
available.
• [851][124] and [125] shall be programmed with time of day for test transmission and 1440 min-
utes (24h) for test transmission cycle
Configuration of communication paths (all ATS classes)
• [300][001] select option 02 for auto routing (this will allow transmission of the events over all
available communication paths in the system)
• [380] enable option 5 (YES) for parallel transmission over all available communication paths
(if redundant configuration is desired)
• [382] enable option 5 (YES) this will enable Alternate communicator
• [384] enable the desired back-up configuration (receiver 2 back-up for receiver 1 or receiver 3
back-up for receiver 1).
Technical Specifications, Ratings and Compatibility
Table 1: Communicator Ratings
Model
Power Supply Ratings
Input Voltage

Current Consumption

Current

Environmental Specifications

Operating Temperature
Humidity

Mechanical Specifications

Board Dimensions (mm)
Weight (grams) with bracket
Table 2: Compatible Receivers, and Panels
Communicator
TL280
NOTE: Enter [*][8][Installer Code][900] at keypad to view the panel version number.
C
OMMUNICATOR
This Ethernet Communicator shall be installed by service persons only (service person is defined
as a person having the appropriate technical training and experience necessary to be aware of haz-
ards to which that person may be exposed to in performing a task and can also take measures to
minimize the risks to that person or other persons). The Communicator shall be installed and used
within an environment that provides the pollution degree max 2, overvoltages category II, in non-
Receiver/
Panel
• Sur-Gard System I Receiver, version 1.13+
• Sur-Gard System II Receiver, version 2.10+
Receiver
• Sur-Gard SG-DRL3-IP, version 2.30+ (for Sur-Gard System III Receiver)
• Sur-Gard SG-DRL4-IP version 1.20+ (for Sur-Gard System IV Receiver)
• Sur-Gard SG-DRL5-IP version 1.00+ (for Sur-Gard System 5 Receiver)
• HS2016
• HS2032
Panel
• HS2064
• HS2128
I
NSTALLATION
Internet Alarm Communicator Installation Guide
10.8-12.5 VDC. Power is supplied from the panel's PC-Link header
or a PCL-422 module in remote cabinet installations. In remote cabi-
net installations, the PCL-422 module located with the communica-
tor is powered by either an HSM2204 or an HSM2300. Refer to the
PCL-422 installation instructions for details.
5% ~ 93% relative humidity, non-condensing
Description
C
2
TL280(R)
100mA @ 13.66V
-10°C to 55°C
100 × 150 × 15
290
ONFIGURATION