In new construction, a smoke detector shall also be installed in
each sleeping room."
2. Mount Smoke Detector Backplate
Mount backplate using screws pro-
vided and the appropriate holes on
the mounting plate.
NOTE: Install wiring in accordance
with the appropriate national and
local electrical codes. For UL/ULC
Installations, the power supply must
be supplied from a UL/ULC Listed
alarm control unit.
CAUTION: The dust cover protects
the unit when not in service. Remove dust cover before use.
The EU and International versions, shall be powered from an
acceptable to the local authorities alarm controller.
3. Wiring
Refer to the wiring diagrams in this installation sheet and
those provided in the Installation Manual of the alarm control
panel being used with the unit. Before connecting the unit,
prepare the wires from the electrical box for connection; Do
not use frayed or bent wire.
9.35-30VDC
V+
V
+ + -
CAUTION: Do NOT use looped wire under terminals. Break
the wire run, to provide supervision of connections.
When wiring is completed, inspect it and correct any errors
before applying power to the unit. When the wiring has been
thoroughly reviewed, neatly insert the wires into the electrical
box and secure the unit to the mounting plate.
To connect this device use only wiring listed as fit for the pur-
pose.
4. Mounting
Detector Installation
Position the detector on to the base
plate using the detector and base plate
alignment marks. Press the detector
gently in place while rotating the detec-
tor clockwise until the detector snaps
into place. Remove the side tab from
the locking tab to lock in place (optional).
Removal: If the side tab is removed to lock the detector,
depress tab with a small flat blade screwdriver and rotate
detector counter-clockwise until the alignment marks line up.
Remove detector.
5. Test Unit
Initiate test for units without a siren by placing a magnet near
the LED/Test Button for greater than 5 seconds. Initiate test for
units with a siren by pressing the test button for greater than 5
seconds.
Alarm activation is indicated by the LED, the siren, and the
alarm reporting to the Control Panel. If the smoke detectors
are inter-connected using model PRM-2W and a detector is
tested, then all detectors will sound. The detector restores to
Locking
Tab
Mounting Holes
EOL Device
+ + -
+ + -
Relay
NO NC C
Mounting
Surface
Alignment
Marks
Detector
CLOSE
OPEN
normal when the test button is released or when the magnet
is removed.
NOTES: Allow a minimum of 20 seconds between test activa-
tions.
If the detector is in one of the following states when a test is
initiated; it will not enter an alarm state.
1. Compensation trouble.
2. Failure of heat or smoke detector.
3. Other internal faults that could prevent a smoke or heat
alarm.
NOTE: Smoke sensitivity of installed detectors can be mea-
sured without removal or an alarm being generated using the
FSD-100 Smoke Detector Test Meter.
Test Unit with FSD-100 Smoke Detector Test Meter
To test the unit using the FSD-100, set the test meter up to
read devices as per the instructions supplied with the test
instrument. Depress the test button (or place the FSD-100 on
the outside edge of the plastics beside the test button to acti-
vate the reed switch on units without siren) on the smoke
detector for 1 second and release.
NOTES: If the test button is held for 5 seconds or longer, an
alarm will be generated. Move the test meter over the center
of the detector, wait until you hear the test meter beep,
remove the unit and the information can be immediately
reviewed. Please see the instructions supplied with the FSD-
100 Smoke Detector Test Meter for more information.
Perform the tests one at a time. Performing simultaneous tests
on multiple detectors may trigger an alarm at the control
panel.
6. Removing the Chamber for Cleaning
To clean or replace the smoke chamber the detector must be
opened.
1. Press the 3 tabs on the bottom of the detector outward to
release.
2. Remove the bottom portion which contains the PCB and
the chamber.
3. Place thumb and forefinger on the sides of the chamber in
the locations indicated by the arrows on top of the cham-
ber.
4. Squeeze gently inward and pull up and the chamber will
Backplate
separate.
Tabs
5. The removable portion can now be replaced or cleaned.
Cleaning can be done using compressed air. Do not use a
cloth as it may leave particles on the inner wall.
6. Replace the new or cleaned chamber by pressing it down
until it snaps into place. Locate and press the backplate
into the housing making sure the 3 locking tabs are
snapped into their locked position.
7. Compensation Reset
Cleaning, replacement of the smoke sensor, or other changes
may change the background signal/noise of the detector; this
requires the drift compensation be reset. Compensation trou-
ble is one of the faults indicated when the LED indicator is OFF
while the siren is chirping.
• Remove power from the unit, then press and hold the test
button for 30 seconds to power down unit.
• Power up unit while pressing the test button.The LED will
flash; when 5 seconds has elapsed. Release the test button
within 1 second after the fifth LED flash.
• The LED will flash every 8 seconds for 1 minute. When the
detector stops flashing test the detector to verify normal
operation.