DSC Meridian MN-220RT Instructies voor installatie en gebruik - Pagina 2

Blader online of download pdf Instructies voor installatie en gebruik voor {categorie_naam} DSC Meridian MN-220RT. DSC Meridian MN-220RT 4 pagina's. 2-wire

Guidelines for Locating Smoke Detectors
On smooth ceilings, detectors may be spaced 9.1m (30 feet) apart
as a guide. Other spacings may be required depending on ceiling
height, air movement, the presence of joists, uninsulated ceilings,
etc. Consult National Fire Alarm Code NFPA 72, CAN/ULC-S553-
M86 or other appropriate national standards for installation
recommendations.
Do not locate smoke detectors at the top of peaked or gabled
ceilings; the dead air space in these locations may prevent the unit
from detecting smoke.
Avoid areas with turbulent air flow, such as near doors, fans or
windows. Rapid air movement around the detector may prevent
smoke from entering the unit.
Do not locate detectors in areas of high humidity.
Do not locate detectors in areas where the temperature rises above
38
o
C (100
o
F) or falls below 5
Figure 1
Bedroom
Bedroom
Bedroom
Living Room
Kitchen
Smoke detectors should always be installed in accordance with NFPA 72, the
National Fire Alarm Code. Smoke detectors should always be located in
accordance with Paragraph 2.1.1.1 of NFPA 72, Chapter 2.:
"2-2.1.1.1 Smoke detectors shall be installed outside of each separate
sleeping area in the immediate vicinity of the bedrooms and on each
additional story of the family living unit, including basements and excluding
crawl spaces and unfinished attics. In new construction, a smoke detector
also shall be installed in each sleeping room."
Figure 3
Bedroom
Bedroom
Living
Dining
Room
Room
Basement
Testing Your Smoke Detector
Test the detector for minimum sensitivity by activating the test feature.
To test the unit, hold the test magnet against the case as shown. The
Alarm Indicator Light will come ON, the Auxiliary Relay (if equipped) will
be activated, and the alarm control panel should indicate a fire alarm.
When the magnet is removed, the Alarm Light and Auxiliary Relay will
remain ON. Turn off the voltage supply from the control panel to the
o
C (41
o
F).
Figure 2
Family Room
Bedroom
Dining
Room
Living
Room
Kitchen
Bedroom
Bedroom
Figure 4
4"
(0.1m)
Ceiling
Acceptable
here
NEVER
HERE
Top of detector
acceptable here
Wall
NOTE: Measurements shown are to
the closest edge of the detector.
detector for two
seconds to reset the
detector to normal.
If
the
smoke
detector does not
function properly,
call your Smoke
Detector Installer or
Dealer for service.
Smoke Sensitivity
may be measured in
a correlated UL268
or CAN/ULC S529-
M87 smoke box. DSC will conduct this test for a nominal charge. If a
returned unit is found outside of its marked sensitivity range, DSC will
clean and restore the unit's sensitivity to its marked range.
Smoke sensitivity of installed detectors can be measured without
removal with the Gemini Model 501 Aerosol Smoke Detector Analyzer.
Follow the instructions supplied with the instrument. Start with the
sensitivity corresponding to the lowest marked detector sensitivity; no
alarm should be indicated. Reset with the highest sensitivity setting;
an alarm should then be indicated. These results indicate that the unit
is within its marked sensitivity range. Other settings can be tried to
bracket the detector's sensitivity to a narrower sensitivity range, such
as may be important during annual tests to quantify any change over
time.
Owner's Maintenance Instructions
The Meridian Smoke Detector is designed to require a minimum of
maintenance. If the case becomes dusty, wipe the case gently with
a soft dry cloth. If the case is greasy, wipe the case gently with a soft
cloth slightly dampened with soapy water.
Never disassemble the smoke detector; there are no user
serviceable parts inside the unit. Never paint the unit, as paint
may prevent smoke from entering the unit. If you are planning
renovations or repainting, contact your Installer and ask that the
unit be temporarily removed until work is complete.
If the unit is located in an area where it is exposed to high levels of
dust or insects and is found to cause false alarms, it may require
service; contact your Smoke Detector Installer or Dealer.
Fire Safety In The Home
Most fires occur in the home, and to minimize this danger, it is
recommended that a household fire safety audit be conducted and
a family escape plan be developed.
Household Fire Safety Audit
4"
(0.1m)
1 Are all electrical appliances and outlets in a safe condition? Check
Max.
for frayed cords, overloaded lighting circuits, etc. If you are
12"
uncertain about the condition of your electrical appliances or
(0.3m)
Max.
household service, have a professional evaluation.
2 Are all flammable liquids stored safely in closed containers in a
cool, well ventilated area? Cleaning with flammable liquids should
be avoided.
3 Are hazardous materials such as matches out of the reach of
children?
4 Are furnaces and wood burning appliances properly installed,
clean and in good working order? If in doubt, have a professional
evaluation.
Family Escape Planning
There is often very little time between the detection of a fire and the
time it becomes deadly. Because of this, it is very important that a
family escape plan be developed and rehearsed.