4. Configuration
4.1 Configuration Menus
Default mode &
Application
Output 1 type
(section 4.2)
(section 4.3.1)
0
Internal sensor
0
Cool / 0-10V
1
Room
1
Heat / 0-10 V
2
Return
2
Cool / 2-10 V
3
Supply
3
Heat / 2-10 V
4
Auto changeover
5
Limited cooling
Application
Default mode
(section 4.2)
(section 4.3.1)
0
Internal sensor
0
Cool
1
Room
1
Heat
2
Return
3
Supply
4
Auto changeover
5
Limited cooling
Default mode &
Application
Output 1 type
(section 4.2)
(section 4.3.1)
0 Internal sensor
0 Cool / 0-10V
1 Room
1 Heat / 0-10 V
2 Return
2 Cool / 2-10 V
3 Supply
3 Heat / 2-10 V
4 Auto changeover
5 Limited cooling
a.
If Output 2 type is set to 0-4, set the SW6 switch to Triac. If the output type is set to 5-8, set the switch to Analog (see section 4.7).
Application
Default mode
(section 4.2)
(section 4.3.1)
0 Internal sensor
0 Cool
1 Room
1 Heat
2 Return
3 Supply
4 Auto changeover
5 Limited cooling
a.
If Output 2 type is set to 0-4, set the SW6 switch to Triac. If the output type is set to 5-8, set the switch to Analog (see section 4.7).
TH150
1A model
Output 1
NSB value
min. opening
(section 5.6)
(section 4.3.2)
1
1°C (2°F)
0
0%
2
2°C (4°F)
1
10%
3
3°C (6°F)
2
20%
4
4°C (8°F)
3
30%
5
5°C (10°F)
4
40%
6
6°C (12°F)
5
50%
7
7°C (14°F)
8
8°C (16°F)
9
9°C (18°F)
1F model
Output 1
NSB value
min. opening
(section 5.6)
(section 4.3.2)
1
1°C (2°F)
0
0%
2
2°C (4°F)
1
10%
3
3°C (6°F)
2
20%
4
4°C (8°F)
3
30%
5
5°C (10°F)
4
40%
6
6°C (12°F)
5
50%
7
7°C (14°F)
8
8°C (16°F)
9
9°C (18°F)
a
Output 3 type
Output 2 type
(section 4.5)
(section 4.4)
0
Not used
0
Not used
1
SSR 24 VAC
1
SSR 24 VAC
2
N.C. Valve
2
N.C. Valve
3
N.O. Valve
3
N.O. Valve
4
Mech. relay
4
Mech. relay
5
SSR 3-32 V
5
Contact
6
SCR 0-10 V
7
Act. 0-10 V
8
Act. / 2-10 V
a
Output 3 type
Output 2 type
(section 4.5)
(section 4.4)
0 Not used
0 Not used
1 SSR 24 VAC
1 SSR 24 VAC
2 N.C. Valve
2 N.C. Valve
3 N.O. Valve
3 N.O. Valve
4 Mech. relay
4 Mech. relay
5 SSR 3-32 V
5 Contact
6 SCR 0-10 V
7 Act. 0-10 V
8 Act. / 2-10 V
Maximum
Minimum
setpoint
setpoint
(section 4.6)
(section 4.6)
Can be set
Can be set
between 35°C
between 10°C
(95°F) and
(50°F) and
''minimum
''maximum
setpoint + 1''
setpoint - 1''
Default value
Default value
is 35°C (95°F)
is 10°C (50°F)
Output 1
Maximum
opening time
setpoint
(section 4.3.3)
(section 4.6)
0
80
1
90
Can be set
2
100
between 35°C
(95°F) and
3
110
''minimum
4
120
setpoint + 1''
5
130
Default value
6
140
is 35°C (95°F)
7
150
8
160
1A2T model
Output 3
NSB value
activation
(section 5.6)
(section 4.5)
0
100%
1
1°C (2°F)
1
10%
2
2°C (4°F)
2
20%
3
3°C (6°F)
3
30%
4
4°C (8°F)
4
40%
5
5°C (10°F)
5
50%
6
6°C (12°F)
6
60%
7
7°C (14°F)
7
70%
8
8°C (16°F)
8
80%
9
9°C (18°F)
9
90%
1F2T model
Output 3
NSB value
activation
(section 5.6)
(section 4.5)
0 100%
1 1°C (2°F)
0 0%
1 10%
2 2°C (4°F)
1 10%
2 20%
3 3°C (6°F)
2 20%
3 30%
4 4°C (8°F)
3 30%
4 40%
5 5°C (10°F)
4 40%
5 50%
6 6°C (12°F)
5 50%
6 60%
7 7°C (14°F)
7 70%
8 8°C (16°F)
8 80%
9 9°C (18°F)
9 90%
Remove the thermostat from its base and
set the SW2 switch to MENU.
Reinstall the thermostat. The thermostat is
now in configuration mode. The first digit
flashes to indicate that the first item of the
menu can now be modified.
To modify the setting, use the up/down
arrows. Refer to the adjacent tables.
Press Override to save the new setting and
go to the next item.
Repeat steps 3 and 4 for remaining items.
When the configuration is done, set the
SW2 switch back to NORMAL.
NOTE: Factory settings are
inside the shaded cells.
Minimum
setpoint
(section 4.6)
Can be set
between 10°C
(50°F) and
''maximum
setpoint - 1''
Default value
is 10°C (50°F)
Output 1
Maximum
min. opening
setpoint
(section 4.3.2)
(section 4.6)
0
0%
1
10%
Can be set
2
20%
between 35°C
3
30%
(95°F) and
4
40%
''minimum
setpoint + 1''
5
50%
Default value
is 35°C (95°F)
Output 1
Output 1
min. opening
opening time
(section 4.3.2)
(section 4.3.3)
0 80
1 90
Can be set
2 100
between
35°C (95°F)
3 110
and ''min
4 120
setpoint + 1''
5 130
6 140
Default
value is
7 150
35°C (95°F)
8 160
400-150-000-C
Minimum
setpoint
(section 4.6)
Can be set
between 10°C
(50°F) and
''maximum
setpoint - 1''
Default value
is 10°C (50°F)
Maximum
Minimum
setpoint
setpoint
(section 4.6)
(section 4.6)
Can be set
between
10°C (50°F)
and ''max
setpoint - 1''
Default
value is
10°C (50°F)
5/9/06
3/6