and press SET will activate the auto-tune. The next setting is the "t" setting, use "-" and
"+" to set the cycle time value. This value should remain 2 for most application. After
change the PID parameter, the controller needs to be turned off and on again for the best
result.
B) The second group is about the system configuration and set up. Once they are set,
they normally do not need to be changed. This group of parameters can be accessed by
input code 155. If you don't want your system to be altered by other people, do not let
others know this code. Table 4 shows the list of the parameters, their range and initial set
value.
Table 4. List of control parameters and the initial settings under code 155
Symbol
Display Description
SC
SC
AL
AL
FA
FA
OAL
OAL
HY
Hy
COOL
COOL
00t
Out
C-F
C-F
Details about each parameter.
 SC, calibration offset. The parameter is used to make the input offset to
compensate for the error produced by sensor. Each unit is 0.1 degree. e.g. if the
temperature displays 2.0 °C in ice water mixture, set SC=-2.0 will make the
display to shown 0.0 degree.
 AL, Alarm temperature in degree. When the temperature passes the alarm set
value, the alarm LED and buzzer will be turned on. When the temperature drops
to that value, the LED and buzzer will be turned off. The alarm is for high limit
alarm only. It will not shut off the out.
 FA. Alarm buzzer control. When FA=1, the buzzer will be on when the alarm
LED is lit. When the FA=0, the buzzer will not be turned on at the alarm
temperature.
 oAL. Open loop alarm. This parameter is for detecting an open loop in the control
system. e.g. if the sensor was forgotten to be inserted in the oven, or the sensor is
defective, or the heater is defective. When enabled (oAL=1), it will shut off the
Off set (degree)
Alarm Setting
Alarm buzzer
Open loop alarm
Hysteresis band
Control mode (heating or cooling)
Output power reduction (%)
Temperature unit
13
Range
Initial
-20.0 ~+20.0
-58.0-392.0°F
-50.0-200.0°C
180.0
0=off 1=on
0
0=off 1=on
0
0-100
0.3
0=heat 1=cool
0
1-100
100
°C or °F
°C