5.4 General
5.5 Key to symbols
5.6 Setting and displaying the
set points
5.7 Level 1 programming
(user level)
10 | BC317523579312en-000101
Defrost Call Icon
12
LED OFF = Defrost call OFF
LED ON = Defrost call ON
LED Flashing = Dripping phase in progress after defrost (see parameter d7)
Auxiliary Relay Icon (AUX relay call signaling if AU1/AU2 = + 2 or + 3)
13
LED OFF = Aux relay call OFF
LED ON = Aux relay call ON
Alarm Icon
14
LED OFF = No alarm in progress
LED ON = Alarm activated then stopped
LED Flashing = Alarm in progress
Decimal Point
15
(flashing in night mode)
16
Hot Mode
(signaling of activation of resistances)
To enhance safety and simplify the operator's work, the AK-RC 113 has two programming levels; the
first level (Level 1) is used to configure the frequently-modified SETPOINT parameters. The second
programming level (Level 2) is for general parameter programming of the various controller work
modes.
It is not possible to access the Level 2 programming directly from Level 1: you must exit the
programming mode first.
For purposes of practicality the following symbols are used:
() the UP key
is used to increase values and mute the alarm.
() the DOWN key
is used to decrease values and force defrosting.
1. Press the SET key to display the current SETPOINT (temperature).
2. Hold down the SET key and press the () or () keys to modify the SETPOINT.
Release the SET key to return to cold room temperature display: the new setting will be saved
automatically.
To gain access to the Level 1 configuration menu proceed as follows:
1. Press the () and () keys simultaneously and keep them pressed for a few seconds until the first
programming variable appears on the display.
2. Release the () and () keys.
3. Select the variable to be modified using the () or () key.
4. When the variable has been selected it is possible:
• to display the setting by pressing SET key.
• to modify the setting by pressing the SET key together with the () or () key.
When configuration values have been set you can exit the menu by pressing the () or () keys
simultaneously for a few seconds until the cold room temperature reappears.
5. The new settings are saved automatically when you exit the configuration menu.