If the build up on the coil consists of only light dust
and debris the condenser coil can be cleaned with
a simple brush, heavier dust build up may require
a vacuum or even compressed air to blow through
the condenser coil.
If heavy grease is present there are de-greasing
agents available for refrigeration use and
specifically for the condenser coils. The condenser
coil may require a spray with the de-greasing agent
and then blown through with compressed air.
Failure to maintain a clean condenser coil can
initially cause high temperatures and excessive
run times, continuous operation with dirty or
clogged condenser coils can result in compressor
failures. Neglecting the condenser coil cleaning
procedures will void any warranties associated with
the compressor or cost to replace the compressor.
CAUTION: Never use a high-pressure water
wash for this cleaning procedure
as water can damage the
electrical components located
near or at the condenser coil.

Gasket Maintenance

Gaskets require regular cleaning to prevent mold
and mildew build up and also to keep the elasticity
of the gasket. Gasket cleaning can be done with
the use of warm soapy water. Avoid full strength
cleaning products on gaskets as this can cause
them to become brittle and prevent proper seals.
Also, never use sharp tools or knives to scrape
or clean the gasket which could possibly tear the
gasket and rip the bellows.
Gaskets can easily be replaced and do not require
the use of tools or authorized service persons. The
gaskets are "Dart" style and can be pulled out of
the groove in the door and new gaskets can be
"pressed" back into place.
Service Manual for Refrigerated Back Counter RBC 48/60

Drain Maintenance - Base

Each unit has a copper drain tube located inside
the unit which removes the condensation from
the evaporator coil and deposits it onto a drain
pan where it can evaporate (See Figure 4). If
you notice excessive water accumulation on the
inside of the unit be sure that the drain tube is
connected from the evaporator housing to the
condensate evaporator drain pan. If water is
collecting underneath the unit you may want to
check the condensate evaporator drain tube to
be sure it is still located above the drain pan.
The leveling of the unit is also important as the
units are designed to drain properly when on a
level surface, if your floor is not level this can also
cause drain problems. Be sure the drain pan is
kept free of dirt, dust and other debris as excessive
amounts will cause water to back up and overflow
from the drain pan.
Location of Drain Tube and Drain Pan
Figure 4