DEVIreg™ 530
• Place the floor sensor in a conduit in an appropriate
place where it is not exposed to sunlight or draft from
door openings.
• Equally distant and >2cm from two heating cables.
• The conduit should be flush with the floor surface -
countersink the conduit if necessary.
• Route the conduit to the connection box.
• The bending radius of the conduit must be min 50mm.
Installation Guide
Note: A floor sensor enables a more accurate
temperature control and is recommended
in all floor heating applications
and mandatory under wooden floors to
reduce the risk of over-heating the floor.