Mounting Guide
Troubleshooting
Error indication
Impossible to add device, ECL, to the Danfoss Link™ CC system
The connection to the ECL is lost
Danfoss Link™ indicates communication error on the ECL and the DLG
for ECL has green light
Flashing LED on DLG
Low room temperature (below comfort settings)
Fejlfinding
Fejlmelding
Ikke muligt at tilføje enhed, ECL, til Danfoss Link™ CC systemet
Forbindelsen til ECL er mistet
Danfoss Link™ melder kommunikationsfejl på ECL og DLG for ECL lyser
grønt
Blinkende udgangs-/alarmlysdioder på DLG
Lav rumtemperatur (under komfortindstillinger)
EC - Declaration of conformity
Hereby Danfoss A/S declares that this equipment is in compliance with the essential requirements and other relevant provisions of
Directive 1999/5/EC.
Danfoss A/S erklærer herved, at udstyret overholder de væsentlige krav og øvrige relevante krav i direktiv 1999/5/EF.
Härmed intygar Danfoss A/S att denna utrustning står i överensstämmelse med de väsentliga egenskapskrav och övriga relevanta
bestämmelser som framgår av direktiv 1999/5/EG.
Hiermit erklärt Danfoss A/S die Übereinstimmung des Gerätes mit den grundlegenden Anforderungen und den anderen relevanten
Festlegungen der Richtlinie 1999/5/EG. (Wien)
Danfoss District Energy
DLG / ECL 110 / Danfoss Link™
Possible Causes
- The distance between the Danfoss Link™ CC and the DLG has
exceeded 1,5m.
- Check if the MODBUS address of the ECL controller is set to 5.
- Check your software version (house control/settings/about) of the
Danfoss Link™ CC and update if older than MkIII 3.2;
http://link.danfoss.com
For further information, see separate instructions for Danfoss Link™ CC
and Danfoss ECL Comfort 110 controller.
- The wireless signal is weak
- Defective device
For further information, see separate instruction
for the Danfoss Link™ CC.
- The cable connection between the ECL and the DLG is unstable / dis-
connected.
- Check if the cable connection between the ECL and the DLG has de-
fects. Fasten the screw terminals and if the error persists the cable has
to be changed.
- The CC is disconnected
- The wireless signal is weak
- Check if the ECL controller is left in setback due to lost connection.
- If connection is ok check the heat curve slope setting of the ECL con-
troller and increase if necessary.
Mulig årsag
- Afstanden mellem Danfoss Link™ CC og DLG overstiger 1,5 meter.
- Kontroller, om MODBUS adressen i ECL regulatoren er indstillet til 5.
- Kontroller, om din softwareversion (huskontrol/indstillinger/om) i
Danfoss Link™ CC og opdater, hvis den er ældre end MkIII 3.2;
http://link.danfoss.com
For yderligere oplysninger, se separate vejledninger til Danfoss Link™
CC eller Danfoss ECL Comfort 110 regulator.
- Det trådløse signal er svagt
- Defekt enhed
For yderligere oplysninger, se separat vejledning
til Danfoss Link™ CC.
- Kabelforbindelsen imellem ECL og DLG er ustabil / afbrudt.
- Kontroller kabelforbindelsen imellem ECL og DLG for defekter. Efter-
spænd skrueterminaler, og vedbliver problemet, skift da kablet.
- CC er afbrudt
- Det trådløse signal er svagt
- Kontroller, om ECL regulatoren er efterladt i reduceret drift pga. tabt
forbindelse.
- Hvis forbindelsen er ok, kontroller den valgte varmekurve i ECL regu-
latoren og hæv den hvis nødvendigt.
VI.JM.C2.6K
DEN-SMT/DK