Danfoss ECL Comfort 296 Bedieningshandleiding - Pagina 11

Blader online of download pdf Bedieningshandleiding voor {categorie_naam} Danfoss ECL Comfort 296. Danfoss ECL Comfort 296 16 pagina's. Return temperature limitation
Ook voor Danfoss ECL Comfort 296: Gebruikershandleiding (12 pagina's), Installatiehandleiding (20 pagina's), Servicehandleiding (16 pagina's), Bedieningshandleiding (8 pagina's), Bedieningshandleiding (10 pagina's), Installatiehandleiding (16 pagina's), Installatiehandleiding (16 pagina's), Installatiehandleiding (16 pagina's), Installatiehandleiding (20 pagina's), Installatiehandleiding (12 pagina's), Installatiehandleiding (16 pagina's), Bedieningshandleiding (8 pagina's)

Danfoss ECL Comfort 296 Bedieningshandleiding
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program
X1 (Start time for period 1)
X2 (Start time for period 2)
X3 (Start time for period 3)
X4 (Start time for period 4)
The time that must elapse from process start for controlling the set
flow temperature in the functional heating period.
Values: Set the times
Example 1:
=
X1
50 hours
=
X2
50 hours
=
X3
200 hours
=
X4
200 hours
Result:
The desired flow temperature, which will be maintained from
process start, is the value, which is indicated / set at X1 in "Desired
flow T".
50 hours after process start, the desired flow temperature, which is
indicated / set at X2 in "Desired flow T", will be maintained.
200 hours after process start, the desired flow temperature, which
is indicated / set at X3 in "Desired flow T", will be maintained.
200 hours after process start, the desired flow temperature, which
is indicated / set at X4 in "Desired flow T", will be maintained.
Example 2:
=
X1
50 hours
=
X2
100 hours
=
X3
150 hours
=
X4
200 hours
Result:
The desired flow temperature, which will be maintained from
process start, is the value, which is indicated / set at X1 in "Desired
flow T".
50 hours after process start, the desired flow temperature will
gradually rise / fall to the value, which is indicated / set at X2 in
"Desired flow T".
150 hours after process start, the desired flow temperature will
gradually rise / fall to the value, which is indicated / set at X3 in
"Desired flow T".
200 hours after process start, the desired flow temperature will
gradually rise / fall to the value, which is indicated / set at X4 in
"Desired flow T".
VI.JM.P2.02
10930
10931
10932
If the functional heating period should not be used, X4 can be set 0
10933
h (zero hours).
© Danfoss | 2017.08 | 11