Danfoss KP 62 Instructies - Pagina 4

Blader online of download pdf Instructies voor {categorie_naam} Danfoss KP 62. Danfoss KP 62 4 pagina's. Vapour charge, adsorption charge (cross ambient)
Ook voor Danfoss KP 62: Installatiehandleiding (2 pagina's), Installatiehandleiding (4 pagina's)

Danfoss KP 62 Instructies
Setting
For KP 61, 62, 63, 68, 69, 71, 73, 75, 77, 79 and 81 w/ AUTO RESET
1. Adjust range spindle to desired
HIGH SET POINT (use hand knob)
2. Adjust diff erential spindle to
desired DIFFERENTIAL
Note:
To fi nd correct diff erential, see "Determination of diff erential"
HIGH SET POINT minus DIFFERENTIAL equals LOW SET POINT
Example:
HSP
DIFF.
=
45°F
10°F
=
(7°C)
(5°C)
KP w/ hand switch
KP 61
060L2003
Vapor charge
KP 73
060L2014
Adsorption charge
4
LSP
35°F
(2°C)
Switch position
Aut.
μ Stop
RI.5D.A2.22 → DKRCC.PI.C0A.A1.22-520H2749
KP 61 and KP 71 w/ MAN. RESET
1. Adjust range spindle to desired
LOW SET POINT
2. DIFFERENTIAL is fi xed.
Value printed on scale plate
HIGH SET POINT minus DIFFERENTIAL equals LOW SET POINT
Example:
HSP
DIFF.
37.4°F
5.4°F
(3°C)
(3°C)
CAUTION:
• Hand switch breaks circuit by micro contact gab.
• Use hand switch for service on refrigeration parts only
• Cut out main switch before service on electrical parts
Contacts position
Automatic control operation
1 and 2 are closed
=
LSP
=
32°F
(0°C)
© Danfoss A/S