Danfoss KP 79 Installatiehandleiding - Pagina 4
Blader online of download pdf Installatiehandleiding voor {categorie_naam} Danfoss KP 79. Danfoss KP 79 4 pagina's. Vapour charge, adsorption charge (cross ambient)
Ook voor Danfoss KP 79: Installatiehandleiding (2 pagina's), Instructies (4 pagina's)
Setting
For KP 61, KP 62, KP 63, KP 68, KP 69, KP 71,
KP 73, KP 75, KP 77, KP 79 and KP 81 w/auto reset
1. Adjust range spindle to desired
HIGH SET POINT (use hand knob)
2. Adjust differential spindle to
desired DIFFERENTIAL
Note:
To find correct differential, see "Determination of differential"
HIGH SET POINT minus DIFFERENTIAL equals LOW SET POINT
Example:
HSP
–
DIFF.
=
7 °C
–
5 °C
=
(45 °F)
(10 °F)
KP w/ hand switch
4
LSP
2 °C
(35 °F)
Switch position
Aut.
µ Stop
DKRCC.PI.CA0.C1.22 / 520H8304
KP 61 and KP 71 w/man. reset
1. Adjust range spindle to desired
LOW SET POINT
2. DIFFERENTIAL is fixed.
Value printed on scale plate
HIGH SET POINT minus DIFFERENTIAL equals LOW SET POINT
Example:
HSP
–
DIFF.
3 °C
–
3 °C
(37.4 °F)
(5.4 °F)
CAUTION:
• Hand switch breaks circuit by micro contact gab.
• Use hand switch for service on refrigeration parts only
• Cut out main switch before service on electrical parts
Contacts position
Automatic control operation
1 and 2 are closed
=
LSP
=
0 °C
(32 °F)
© Danfoss A/S (AC-MCI / jmn), 2013-11