When the monobloc is powered up for the first time, 1-100% will be displayed on the user interface during
initialisation, in this time the controller can't be used.
The following setting must be entered into the controller these are detailed below, in order for the controller and Heat
pump to operate correctly.
Press and Hold the unlock button for 3 seconds.
Press the menu button to enter the menu
Scroll down the using the down arrow to SERVICEMAN and press OK
Enter the SERVICEMAN code 234.
Select DHW MODE SETTING
Set DHW Mode to
DISINFECT should be set
immersion is controlled by the
heat pump.
DHW PRIORITY should be set to
1.18 t_DHWHP_MAX should be set
According to the tank size:
200L - 60min
300L - 90min
All changes to selections must be confirmed with
Press BACK
Select Cool Mode
Cool Mode 2.1 should be set to
All changes to selections must be confirmed with
Press BACK
Select Heat Mode
Set T1setH1, set to 55֯ c for Rads and 45֯ c
for UFH or to the Design flow temp.
Set T1SetH2, set to 30֯ c
Set T4H1, set to the External design temp
We recommend -2֯ c or -5֯ c for Scotland
W: www.aukdistribution.com
Starting Up the Unit for the First Time
YES
YES
if the
Yes
NON
T: 0191 516 6553
FOR SERVICEMAN