Duomo BX316 Handmatig - Pagina 7

Blader online of download pdf Handmatig voor {categorie_naam} Duomo BX316. Duomo BX316 11 pagina's.

Use the up and down keys on the keypad to move
through the events as shown below.
- E v e n t 0 1 -
2 3 / S e p / 1 1
P r o b e 1 0
V = 0 2 . 9 V
Pressing the
or
recorded events one by one. Pressing the
will scroll down/up through five events at a time.
The meaning of the various events is as follows;
Pre-Alarm
The probe stated on the screen has entered pre-alarm
on the date shown and returned the voltage and
current stated.
Alarm
The probe stated on the screen has entered alarm on
the date shown and returned the voltage and current
stated.
Fault
There is a fault with the indicated sensor.
Blackout
Power to the BX216 has been lost. Check incoming
230V power supply.
Reset
The BX216 has been reset using the button on the
fascia following an alarm condition.
Low Battery
The backup battery (not supplied) is running low.
Probe Enabled
The sensor indicated has been enabled using the
internal setup.
Prove Disabled
The sensor indicated has been disabled using the
internal setup.
Hard Reset
The BX216 has been completely reset using the
internal setup. All internal data has been reset
(including sensor setup).
When you reach the end of the datalogger, select Back to
return to the previous menu.
B a c k
w: www.duomo.co.uk
-
1 1 : 5 8
P r e - a l .
I = 1 8 . 9 m A
key will scroll down/up through
or
Print
Select this option to print information contained within
the BX216. (NOTE: These options will only be available
when a printer is connected. Printer not included).
P r i n t s t a t u s
P r i n t d a t a l o g g e r
B a c k
key
There are two options within this menu; print status and
print datalogger.
'Print status' will print the current status of all zones. It
will show whether or not a sensor is attached and if one
is, what state it is currently in.
'Print datalogger' will print the entire contents of the
datalogger, showing you all events recorded by the
BX216.

Test Probes

This option shows the voltage and current readings of
the return signals from any attached sensor.
V = 0 0 . 6 V
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
T E
x x x x x x x x x x x x x x
B a c k
V = 0 0 . 6 V
1 2 3 4 5 6 7 8
T E
x x x x x x
B a c k
Engineers can use this information to ascertain the
accuracy of the attached sensors and determine if they
need calibrating / trimming. Select Back to return the
previous menu.

Factory Reset

Select this option, then press and hold Enter for 4
seconds until you see the screen below appear.
F a c t o r y r e s e t
B a c k
Continue to hold Enter and the bars will gradually fill in
from left to right until they are all filled white. At this
point the unit will turn itself off and on again and the
factory reset will be complete.
Select Back to return the previous menu.
-