Duomo CO233/A Installatie- en gebruiksaanwijzing - Pagina 4

Blader online of download pdf Installatie- en gebruiksaanwijzing voor {categorie_naam} Duomo CO233/A. Duomo CO233/A 4 pagina's. Carbon monoxide gas sensor

Display Indications
0
ppm
CON
FAU
Positioning of the Sensor
CO233/A
autosetting
8
7
6
5
4
3
2
1
Detection
Carbon Monoxide
Important Notes
IMPORTANT: Assembly / maintenance of the appliance must be carried out by qualified personnel and in
accordance with applicable laws and regulations.
The manufacturer assumes no responsibility for the use of products that have to comply with particular
environmental and / or installation standards.
IMPORTANT: Before connecting the equipment, it is recommended that you read the instruction manual
carefully and keep it for future reference.

Troubleshooting

If the device does not start up.
Check that the 12/24 VDC power is present, and that positive and negative polarity has not been inverted.
If the Fault LED condition occurs.
Check that the cables are connected according to the drawing, and that the wire isolation sheath has not been pinched.
Check the voltage at the terminals 1-2. It must be higher than 11 VDC and lesser than 25VDC.
Check the voltage at the terminals 2-3. It must be from a minimum of 0.8 VDC to a maximum of 1.1 VDC.
13122018.Rev3
CO233/A - Carbon Monoxide Gas Sensor
GREEN
When the display is Green in colour with a gas
concentration in parts per million (ppm). This indicates
that the toxic gas threshold has not been exceeded.
WHITE
When the display shows the White colour and text 'Con'
is shown. It indicates that the testing instrument is
connected.
YELLOW
When the display shows the Yellow colour and text
'FAU' is shown. It indicates a sensor fault. This
immediately triggers the fault relay.
Duomo (UK) Ltd | Tel: 01905 797989 | email: [email protected] | web:
Sta
8HA
300
ppm
The position of the sensor is a crucial factor for its correct
functioning. The sensor must be placed at a height of:
160 cm from the lowest point on the floor up to 30 cm
from the ceiling, and in all cases at an average height in
the monitored area.
The sensor must not be placed near the following:
furnaces, fuel-burning kitchen appliances, fireplaces,
ranges, suction fans, and should not be affected by
smoke, vapour as these could distort its measurement.
The sensor must not be placed away from sources of
heat, suction fans, ventilation fans, windows, doors, etc.
that can distorting the detection, should be placed away
from heat sources and away from aspirators or fans.
Duomo (UK) Limited - Worcestershire, England
MAGENTA
When the display shows the Magenta colour and text
'StA' is shown. It indicates that the maximum average
concentration to which an unprotected worker may be
exposed in any fifteen-minute interval during the day
has been detected (200ppm) and the main alarm relay
has triggered.
CYAN
When the display shows the Cyan colour and text '8hA'
is shown. It indicates the maximum average
concentration to which an unprotected worker may be
exposed in any eight-hour interval during the day has
been detected (30ppm) and the main alarm relay has
triggered.
RED
When the display shows the Red colour and a gas
concentration in ppm is shown. It indicates the toxic
gas threshold has been reached or passed. If the 300
ppm has detected the main alarm relay is triggered
immediately.
www.duomo.co.uk
4