DANLERS DIN RFS Installatie-opmerkingen
Blader online of download pdf Installatie-opmerkingen voor {categorie_naam} DANLERS DIN RFS. DANLERS DIN RFS 2 pagina's. Radio receiver switches
Preprogrammed options
DANLERS radio receiver switches can be factory programmed, with the
associated senders, to perform more complex functions, such as:
• On - Auto Off after set time period
- with Manual Off
- with flashing warning 15 seconds before Auto Off
• Delayed Off or On, momentary On or flashing On
• Toggle On - Off with same button.
Fault finding
Radio receiver switch does not respond to sender:
• Ensure the sender is correctly associated to the radio receiver.
• The sender is too far away or RF absorbed by building or trees.
Move sender closer to receiver or consider using a repeater.
• The sender battery is flat (average life approx. 5 years).
Change battery, make reference to sender installation notes.
Load and receiver LED flash twice every time the sender is pressed:
• Ensure the radio receiver switch is not in programming mode.
Radio receiver relay clicks but load does not switch on / off:
• The load or in-rush current is too large and has damaged receiver.
Use a contactor to switch over limit loads.
Precautions and Warranty
This product conforms to BS EN 60669-2-1.
Please ensure the most recent edition of the appropriate local wiring regulations are observed
and suitable protection is provided e.g. 6 amps over current, 1kV over voltage. Please ensure
that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
Please call for more information or a free catalogue, or visit our website.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
E-mail: [email protected]
Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
27/01/11
Radio receiver switches
WACE RFS
CEVO RFS
DANLERS radio receiver switches can be user programmed to respond
to any DANLERS radio frequency (RF) manual (or slave) senders.
With a manual sender the radio receiver switch will switch the load
on when an associated up button is pressed and switch the load off
when the down button is pressed.
With a slave sender the radio receiver switch will follow the state of
the input signal to the slave sender.
To dim a load use a radio receiver dimmer instead.
Mounting examples
WACE RFS
CEFL RFS
DIN RFS
EX RFS
CEVO RFS
CEVO RFS6A Ceiling Void, fits cutout ø 90mm (55 x 75 x 130mm)
CERF S6A
PORF S8A
Loading limits
Suffix
RFS
S6A
S8A
Connection method
WACE, DIN, EX Via incorporated terminals
CEFL, CEVO
CERF
PORF
INS960 RFS
CEFL RFS
DIN RFS
CEVO RFS6A
CERF S6A
Wall or Ceiling mounted onto a 16mm deep back box
Ceiling Flush (cutout ø 63mm) or in ceiling void
Din rail mounting (w x h x d: 36 x 75 x 100mm)
External unit - rated to IP65
Ceiling Void, fits cutout ø 60mm (35 x 55x 90mm)
Ceiling mounted to Klik-AX socket. Order:
Portable unit for plugging into square 3-pin socket
Resistive
Fluorescent Fans
1500W
250W
250W
1500W
1500W
250W
2000W
250W
250W
Via 2 metre flex
Klik-AX socket (round:
Plugs into square 3-pin power socket
Installation notes
EX RFS
PORF S8A
CESO(SQ)
square:
CESO,
CESO SQ)