DANLERS BMPIRRH Installatie-opmerkingen
Blader online of download pdf Installatie-opmerkingen voor {categorie_naam} DANLERS BMPIRRH. DANLERS BMPIRRH 2 pagina's. Batten mount pir occupancy switches
Wiring diagram
BMPIR5M/10M/SP/RH
L
optional manual
wall switch for
overriding off
230 VAC
N
Trouble shooting
The PIR does not detect
• Person is too far from the PIR switch, see detection diagram.
• Person is moving unusually slowly (perhaps when testing).
The PIR false triggers
• Detector is placed too close to heat or moving air sources.
Precautions and Warranty
This product conforms to BS EN 60669-2-1.
Please ensure the most recent edition of the appropriate local wiring regulations are observed
and suitable protection is provided e.g. over current protection, 1kV over voltage. Please ensure
that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
Please call for more information or a free catalogue.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
E-mail: [email protected]
Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
19/08/13
SL
N
load
INS713 BMPIR5M / 10M / SP / RH
Batten Mount PIR occupancy switches
BMPIR5M
BMPIR10M
DANLERS Batten mount passive infra-red occupancy switches (PIR)
can be mounted onto the end of lighting battens via the 20mm knock
out. The switch includes the connection 20mm thread and 1m of wire
tails to connect to the lighting ballast.
The PIRs incorporate a passive infra-red quad sensor to detect
movement of a warm body within the detection zone and include a
photocell to monitor the ambient light level.
On detecting movement, if the ambient light is dark enough, the PIR
will switch the load on. The ambient threshold can be set by the user
to between approximately 100 and 3000 lux (on the working plane)
via the LUX adjuster.
BMPIR5M has a 5m diameter range, 5m max height, see diag. B.
BMPIR10M has a 10m diameter range, 5m max height, see diag. B.
BMPIRSP has a 1.5m diameter range, 5m max height, see diag. B.
BMPIRRH has a 2.5m diameter range, 2.5m max height, see diag. B.
A 'real time' photocell status indicator glows green when the photocell
is active and glows red when the photocell is inactive.
If no more movement is detected within a certain time, then the PIR will
switch off the load. The time can be set via the internal TIME adjuster
to between 10seconds and 40 minutes (diagram D).
Loading
These PIRs should only be connected to a 230V 50Hz ac supply.
They can switch the following type of loads:
• 10 amps (2500W) resistive loads and tungsten
• 6 amps (1500W) fluorescent (switch start) / mains halogen lamps
(recommended with integral safety fuse)
• 3 amps (750W)
Electronic or wire wound transformers.
Compact fluorescent or LED lamps.
Normally OPEN contacts.
Installation notes
BMPIRSP
BMPIRRH