AEZ GCM02 Handmatig - Pagina 11
Blader online of download pdf Handmatig voor {categorie_naam} AEZ GCM02. AEZ GCM02 12 pagina's. Automatic microprocessor control panel for stand-by generator
1.6 PROGRAMMING
If the electronic module should be disconnected from the power supply, the established weekly timer programming will be
deleted; consequently, all the functions foreseen for the internal timer would fail to work at the time and on the programmed
day, therefore, the weekly timer has to be re-programmed.
When a function - the automatic test, the automatic lock or the automatic start – is enabled, the following screen will appear
on the display in case the battery is not driven any more:
FUNCTIONING OROL.....
Go to the following page re-program it.
Pressing ENTER, the day flashes. Using the +/- keys, modify the day and press ENTER to confirm. The time flashes.
Using the +/- keys modify the time and confirm with ENTER. Do the same for minutes and seconds.
In case of uncomplete programming it is impossible to change the page.
1.7 VARIOUS CONTROLS
LED TEST
Press the + /- push buttons together for 2 seconds. All LEDs, except the start, stop and battery charger LEDs, will light up.
ALARM SILENCING
Press the RESET key for 2 seconds to silence the buzzer alarm.
FUNCTIONS RESET
Press the RESET key for 2 seconds to reset the alarm status and to restore the functions.
1.8 SPECIAL FUNCTIONS
The M02 is preset for some special operating functions such as: automatic test and lock, scheduled maintenance,
remote assistance ecc. if enabled, when they start functioning, on the display a screen, indicating the enabled function,
appears. Some functions influence the set operativeness and need direct interventions in order to use the group.
LOCKED GE
The lock function is principally used when a set operates in town and the emergency is not requested at night. When
locked, in case of mains lack the set will not work. If its intervention is needed, it will be only possible using the manual
Controls.
MAINTENANCE REQUEST
It does not alter the functioning, enables the acoustic alarm status for the fixed time and shows the word MAINTENANCE
on the display.
FILE
VER
LAST ISSUE
LANG.
PAGE
GCM02-M-USO-INGLESE.doc
SDG/02
18/11/2005
ENG
Page 11 of 12