Data Aire, Inc. DAP

4.2 Analog Input Objects

4.2.1 Readable fields

Object-identifier
Object-name
Object-type
Present-value

4.2.2 Object List

Object Name
Return Air Temperature
Relative Humidity
Discharge Air Temperature
Chilled Water Temperature
(Optional)
Analog Input 1 Sensor
(Optional)
Analog Input 2 Sensor
(Optional)
Analog Input 3 Sensor
(Optional)
Analog Input 4 Sensor
(Optional)

4.3 Analog Value Objects

4.3.1 Readable fields
Object-identifier
Object-name
Object-type
Present-value
Engineering Document - 600-000-460
TM
III BACnet Integration Instructions
Status-flags
Event-state
Out-of-service
Units
Instance
No. AI
1
Current Return Air temperature
2
Current Relative humidity
3
Current Discharge Air temperature. This
temperature is only available when an
optional Discharge Air sensor is installed
4
Chilled Water temperature. This
temperature is only available when an
optional Chilled water sensor is installed.
5
An optional analog sensors such as
temperature transmitter must be installed
and programmed into analog module
input 1
6
An optional analog sensor such as
temperature transmitter must be installed
and programmed into analog module
input 2.
7
An optional analog sensors such as
temperature transmitter must be installed
and programmed into analog module
input 3
8
An optional analog sensors such as
temperature transmitter must be installed
and programmed into analog module
input 4
Status-flags
Event-state
Out-of-service
Units
Page 10 of 13
Object Name
Present-
Value
Writeable
No
No
No
No
No
No
No
No