6

CIRCUITRY

Relieve the various cables (the ones connected to the alarm transmitter) of stresses by
securing them outside the encasement, approximately 10 centimeters away. The plastic
encasement also has prepared holes for cable ties on the bottom of the case.
6.1

Fire alarm installation (EN 54-21:2006)

Connect relay 3 (for error indication) to the control panel. See 6.5.1 for connection
instructions as well as a data sheet (see 10) for details regarding the signaling and levels
of the output.
Connect relay 4 (for alarm acknowledgments from the alarm receiver) to the control
panel. See 6.5.2 for connection instructions as well as a data sheet (see 10) for details
regarding the signaling and levels of the output.
Connect the control panel's output for error indication to optional alarm input.
Balance the output from the control panel with 4.7kΩ.
6.2

Alarm installation (EN 50136/SSF 114)

To meet security grade 3, the removal detector must be mounted. See the included instructions
on how to mount it (Installation manual – Removal detector 47IN0051).
Connect relay 3 (for error indication) to the control panel. See 6.5.1 for connection
instructions as well as a data sheet (see 10) for details regarding the signaling and levels
of the output.
Connect relay 4 (for alarm acknowledgments from the alarm receiver) to the control
panel. See 6.5.2 for connection instructions as well as a data sheet (see 10) for details
regarding the signaling and levels of the output.
6.3

Power supply

PIN
1
Primary voltage supply
+12V to + 30V DC, with 2A fuses at 12V DC
2
Ground
3–4
Not used
5
Secondary voltage supply
See pin 1
6
Ground
Figure 5 - Power
supply terminal
block
AddSecure Tor V, PDK-11606