DISPLAY
DESCRIPTION
FAN OFF PARAMETER ()
Adjusts Fan Turn OFF Temperature.
ALARM ENABLE PARAMETER
()
0: No alarm is generated from this
channel
1: if the temperature read from this
channel is over Alx limit, then an alarm is
generated.
RS-485 DATA RATE: (bdr)
0: 2400 baud
1: 4800 baud
2: 9600 baud
3: 14400 baud
4: 19200 baud
MODBUS NODE ADDRESS (nod)
This parameter defines the address of
the unit in a Modbus network. Each
device in the same network must have a
different address.
For any channel, the difference between Alarm and Trip
temperatures cannot be less than 5 degrees C and the Trip
temperature is always higher than Alarm temperature.
The same way, the difference between Fan Turn ON and Turn
OFF parameters cannot be less than 5 degrees C and Fan
Turn ON is always higher than Fan Turn OFF.
5: 28800 baud
6: 38400 baud
7: 56000 baud
8: 57600 baud
9: 115200 baud
-15-
V-3.0
(14.09.2016)
MIN
MAX
0
295
0
1
0
9
0
255