Elsist Pure 1000 Gebruiksaanwijzing - Pagina 13
Blader online of download pdf Gebruiksaanwijzing voor {categorie_naam} Elsist Pure 1000. Elsist Pure 1000 18 pagina's. Single phase line interactive sinewave ups
PURE 1000●2000●3000
LINE INTERACTIVE SINGLE-PHASE
SINEWAVE
3.6 Setting parameters
In normal mode, press the UP / MENU key for at least two seconds to enter the settings menu. Press the UP -
DOWN keys to scroll through the available menus (blinking written). Press for two seconds to enter the options
of the chosen parameter, scroll through the available parameters using the UP - DOWN keys. Confirm the
parameter by pressing the UP / MENU key for two seconds and press for another two seconds to exit. Repeat
the sequence to make other changes.
If no command is made within 50 seconds, the display returns to the initial screen.
ITEM
OPU
(Output Voltage)
Abt
(Automatic Battery
Test)
bPS
(ByPass)
ISt
Eod
(End of Discharge)
Ver.00 09 March 2018
DESCRIPTION
Selectable Output Voltage.
Available selections:
208V - 220V - 230V - 240V.
Available selections: ON or OFF.
When ON is selected, the UPS
performs a battery test every 30
days
for
about
10
Selecting OFF deactivates the
function.
Available selections: ON or OFF.
When ON is selected, the Bypass
function is enabled, When OFF is
selected it is disabled.
Available selections: 10.5 - 11.0 -
11.5. The UPS is equipped with
two series of output sockets,
SEGMENT1 and 2 as described in
chapter 2.1 and 2.3. When the
battery voltage reaches this value
the UPS will cut off voltage at the
SEGMENT1
output
(non-critical loads).
Available selections: 9.5 - 10.0 -
10.5 - 11.0.
When the battery voltage reaches
this value the UPS does not
supply more output voltage.
seconds.
sockets
GRAPHIC
13