Dataprobe iBoot Handmatig - Pagina 15

Blader online of download pdf Handmatig voor {categorie_naam} Dataprobe iBoot. Dataprobe iBoot 20 pagina's. Web enabled remote power control
Ook voor Dataprobe iBoot: Gebruiksaanwijzing (16 pagina's)

Dataprobe iBoot Handmatig
iBoot Ver 1.5
Ping Address: Enter the IP address of the device to be pinged.
Ping Frequency: Enter 1 to 999 seconds. The ping will go out to the selected
device this often.
Fail Counter: Enter 1-99 times the ping needs to fail before the selected action
is taken.
Action: select from
None (Auto Ping not used)
Power On – Latch
Power On – Follow
Power Off – Latch
Power Off – Follow
Power Cycle
Power Cycle Once
Power On – Latch: Upon loss of ping response, iBoot will power on and remain
so until changed via the web, ibootctl.exe or direct messaging.
Power On – Follow: Upon loss of ping response, iBoot will power on. When the
ping response returns, iBoot will power off.
Power Off – Latch: Upon loss of ping response, iBoot will power off and remain
so until changed via the web, ibootctl.exe or direct messaging.
Power Off – Follow: Upon loss of ping response, iBoot will power off. When the
ping response returns, iBoot will power on.
Power Cycle: Upon loss of ping response, iBoot will cycle the power. iBoot will
wait the Ping Frequency; if the response does not return, the power will be
recycled again. This will continue until the ping response returns or Auto Ping is
turned off. Make sure your Auto Ping frequency is longer than the time required
to reboot your device.
Power Cycle Once: Upon loss of ping response, iBoot will cycle power one time.
It will not cycle again automatically until the ping response returns and is lost
again.
Home:
Return to the main screen
Remember to click Apply for each section you are changing.
Upon Clicking Reboot, a page
indicates the new URL for the
device. Use this new URL to
access iBoot.
Page 15