iPIO-xx Unit
Network Cable
Quick Start Guide
A/C Power Supply
Connections
1.
Connect Network.
5) cabling. When power is connected to the iPIO, the green Activity LEDs on the network connector indicates when the
network connection is properly established.
2.
Connect Inputs.
Connect the inputs to the iPIO using the screw terminals.
Inputs can be either dry relay or switch contacts, or a +VDC
voltage (3 to 30 V), referenced to a common ground.
Screw terminals are removable for easy installation.
Terminals for each circuit are marked + and G.
connecting dry relay contacts, the polarity is not significant.
3.
Connect Relays.
Relays are Form C.
Normally Closed (NC) and Normally Open (NO) as
marked. When the iPIO-8 relay is in the Open Condition,
the Common is connected to the Normally Open. In the
Closed state, the Common and Normally Closed are
connected.
4.
Connect Power.
Power supply.
power up the iPIO device. The iPIO-2 supports Power
over Ethernet (PoE). Consult the complete manual for more details.
.
IPIO quick start
Quick Start Guide
iPIO supports 10/100 Ethernet using the cable supplied, or other suitable unshielded twisted pair (Cat
(2 Connections per Channel)
(3 Connections per Channel)
Connect to the Common (C),
Each unit is supplied with a n A/C
Connect to suitable A/C source, then
Available Online at
dataprobe.com/support-ipio
When
Relay Specifications
Rating (resistive)
Max Carrying Current
Max Switching Power
Max Switching Voltage
Max Switching Current
Life Expectancy
© 2018 Dataprobe Inc.
Complete Product Manual
Device Management Utility
Latest Firmware
Software Developer Tools
The iPIO is Factory set for Dry
Contact Input Only.
Prior to Connecting +VDC, Jumpers
must be configured.
See full manual or contact Dataprobe
Technical Support.
0.5 A 120 VAC or
1 A 24 VDC
2 A
60 AV, 24 W
120 VAC/60 VDC
1A
5 Million Operations Mech.
100K Oper. at rated load
V180802E