Bender NGRM700 Snelstarthandleiding - Pagina 2

Blader online of download pdf Snelstarthandleiding voor {categorie_naam} Bender NGRM700. Bender NGRM700 8 pagina's. Neutral grounding resistor monitor (ngr)
Ook voor Bender NGRM700: Snelstarthandleiding (8 pagina's), Snelstarthandleiding (8 pagina's), Handmatig (8 pagina's)

NGRM700 (HRG), NGRM750 (LRG)
Intended use
The NGRM700 is only intended for use in high-resistance
grounded systems. The NGRM750 is only intended for
use in low-resistance grounded systems. In these sys-
tems, the NGRM7... monitors
• the current through the neutral grounding resistor
(NGR),
• the voltage between the star point of the transform-
er and ground (voltage drop across the NGR),
• the condition of the NGR,
• line-to-line and line-to-earth voltages.
This quick-start guide does not replace the operating
manual of the device. Download: www.bender.de/manu-
als
Quick-start guide for
Type
NGRM700
NGRM750
Removing the FP200-NGRM
PH 1
Connection X1
2
NGRM7xx_D00292_07_Q_XXEN/11.2022
Supply voltage/Frequency range U
AC 24...240 V, 40...70 Hz
DC 24...240 V
1
X1
ETH
R
I1
I1
Digital 1 (configurable: pulser, NGR method)
I2
I2
Reset IN
I3
A
I3
Test IN
B
A
Modbus RTU (A)
B
Modbus RTU (B)
Common
M+
Analog output
Q2
Open Collector: Pulser OUT
M+
Q2
Q1
Open Collector: Device health
Q1
+
Output for supply of external relays (+24 V, max. 100 mA)
+
Safety instructions
I
of electrocution due to electric shock!
R
isk
Touching live parts of the system carries the risk of:
- An electric shock
- Damage to the electrical installation
- Destruction of the device
B
efore installing the device and before working on its
,
make suRe that the installation has Been
connections
-
. O
de
energized
bseRve the Rules fOR wORking On
electRical installatiOns
S
X1
ETH
R
OFF
ON
.
Art. No.
Manual
B94013700
D00292
B94013750
RJ45:
Remote
max. 5 m
Switch
RJ45:
Ethernet