Bender COMTRAXX CP305-IO Snelstarthandleiding - Pagina 7
Blader online of download pdf Snelstarthandleiding voor {categorie_naam} Bender COMTRAXX CP305-IO. Bender COMTRAXX CP305-IO 8 pagina's. Remote alarm indicator for medical locations and other areas
Ook voor Bender COMTRAXX CP305-IO: Snelstarthandleiding (8 pagina's)
Technische Daten
Bemessungsspannung ......................................................... 50 V
Überspannungskategorie ......................................................... II
Versorgung ................................. über Steckklemme A1/+,A2/-
Versorgungsspannung .............................................. AC/DC 24 V
Arbeitsbereich U
.......................... AC 18...28 V / DC 18...30 V
S
Nennfrequenz ............................................................. 50/60 Hz
Max. Leitungslänge (24 V DC-Netzteil 1,75 A)
0,28 mm² .................................................................75 m
0,5 mm² .................................................................130 m
0,75 mm² ...............................................................200 m
1,5 mm² .................................................................400 m
2,5 mm² .................................................................650 m
Leistungsaufnahme ......................................................< 4,2 W
Schaltglieder (nur CP305-IO)
Anschluss ....................................................Steckklemme
K1 NC; K1 NO; K1 COM / K2 NC; K2 NO; K2 COM
Anzahl Wechsler ............................................................2
Arbeitsweise (Wechsler) ..................................................
...............................Ruhestrom (N/C)/Arbeitsstrom (N/O)
Funktion ................................................programmierbar
Elektrische Lebensdauer ........................ 10.000 Schaltspiele
Kontaktdaten nach IEC 60947-5-1
Gebrauchskategorie ......................... AC-13/AC-14/DC-12
Bemessungsbetriebsspg. ...........AC 24 V/AC 24 V/DC 24 V
Bemessungsbetriebsstrom ............ AC 2 A/AC 2 A/AC 2 A
Anzeige ...............................5" TFT-Touchdiplay (720 x 1280 px)
Front ...................Glas, gehärtet, IP66 (UL-Anwendungen: IP50)
Maße............................................................181 x 96 x 37,1 mm
Gewicht .......................................................................... < 420 g
Weitere Bestellnummern
Zubehör
Typ
Unterputzgehäuse
Aufputzgehäuse CP305
Hohlwand-Montageset für
Unterputzgehäuse
CP305 Stecker Kit
CP305-IO Stecker Kit
Ethernet Adapter Kit
(RJ45-Buchseneinsatz, Cat.6
SLIM Patchkabel)
Das CP305 ist für den Einsatz in grundlegenden
(DIN EN 61326-1, Tabelle 1) und industriellen
(DIN EN 61326-1, Tabelle 2) elektromagnetischen
Umgebungen vorgesehen.
Montage
Art.-Nr.
Unterputzmontage
B923710
Aufputzmontage
B95100153
Hohlwandmontage
B923711
B95100150
B95100151
B95100152
Technical data
Rated voltage ....................................................................... 50 V
Overvoltage category ............................................................... II
Supply .......................................via plug-in terminal A1/+,A2/-
Supply voltage .......................................................... AC/DC 24 V
Operating range of U
................... AC 18...28 V / DC 18...30 V
S
Nominal frequency ...................................................... 50/60 Hz
Max. cable length (24 V DC power supply unit 1.75 A)
0,28 mm² .................................................................75 m
0.5 mm² .................................................................130 m
0.75 mm² ...............................................................200 m
1.5 mm² .................................................................400 m
2.5 mm² .................................................................650 m
Power consumption ......................................................< 4.2 W
Switching elements (CP305-IO only)
Connection ............................................Plug-in terminal
K1 NC; K1 NO; K1 COM / K2 NC; K2 NO; K2 COM
Number of changeover contacts .....................................2
Operating principle (changeover contacts) ......................
......................................... N/C operation / N/O operation
Function ................................................... programmable
Electrical endurance ............................... 10.000 Schaltspiele
Contact data acc. to IEC 60947-5-1
Utilisation category ......................... AC-13/AC-14/DC-12
Rated operational voltage. ........AC 24 V/AC 24 V/DC 24 V
Rated operational current .............. AC 2 A/AC 2 A/AC 2 A
Display ..............................5" TFT touch display (720 x 1280 px)
Front ..................glass pane, hardened, IP66 (for UL appl.: IP50)
Device dimensions (W x D x H) .................... 181 x 96 x 37.1 mm
Weight .......................................................................... < 420 g
Other order numbers
Accessories
Type
Flush-mounting enclosure
Surface-mounting enclosure
CP305
Cavity wall installation set for
flush-mounting enclosuree
CP305 plug kit
CP305-IO plug kit
Ethernet adapter kit (RJ45 socket
insert, Cat.6 SLIM patch cable)
The
CP305
is
intended
(DIN
EN
61326-1,
(DIN EN 61326-1, Table 2) electromagnetic environ-
ments.
CP305_D00425_00_Q_DEEN / 09.2022
Mounting
Art. No.
Flush-mounting
B923710
Surface-
B95100153
mounting
Cavity wall
B923711
installation
B95100150
B95100151
B95100152
for
use
in
Table
1)
and
industrial
basic
7