Bender B73010003 Snelstarthandleiding - Pagina 7

Blader online of download pdf Snelstarthandleiding voor {categorie_naam} Bender B73010003. Bender B73010003 8 pagina's. Multi-functional monitoring relay for undervoltage, overvoltage and frequency monitoring in ac/dc systems without separate supply voltage

Bender B73010003 Snelstarthandleiding

Technische Daten

Tabellarische Daten
( )* = Werkseinstellung
Isolationskoordination nach IEC 60664-1/IEC 60664-3
Bemessungsspannung ........................................................250 V
Bemessungs-Stoßspannung / Überspannungskategorie 4 kV / III
Verschmutzungsgrad .................................................................3
Sichere Trennung (verstärkte Isolierung) zwischen: ....................
...................................... (U1/+, U2/-) - (11-12-14) - (21-22-24)
Spannungsprüfung nach IEC 61010-1 .............................. 2,21 kV
Versorgungsspannung U
VME421H-D-1 ........
keine (interne Versorgung aus U
VME421H-D-2 ........
keine (interne Versorgung aus U
Eigenverbrauch ............................................................... ≤ 6 VA
Messkreis
Messbereich (Effektivwert)
VME421H-D-1 ........................................... AC / DC 0...150 V
VME421H-D-2 ............................................ AC / DC 0...300 V
Bemessungsfrequenz f
.....................................DC, 15...460 Hz
n
Frequenzanzeige .....................................................10...500 Hz
Schaltglieder
Anzahl .....................................................2 x 1 Wechsler (K1, K2)
Arbeitsweise .......................................Ruhestrom / Arbeitsstrom
K2 ......................................... Err, < U, > U, < Hz, > Hz, S.AL
..................................(Unterspannung < U: Ruhestrom n.c.)*
K1 ......................................... Err, < U, > U, < Hz, > Hz, S.AL
............................... (Überspannung > U: Arbeitsstrom n.o.)*
Elektrische Lebensdauer bei Bemessungsbedingungen
....................................................................... 10000 Schaltspiele
Kontaktdaten nach IEC 60947-5-1
Gebrauchskategorie ..............................................................
.........................AC 13..... AC 14 ..... DC-12 .... DC-12..... DC-12
Bemessungsbetriebsspannung . ............................................
........................ 230 V..... 230 V ........ 24 V ..... 110 V..... 220 V
Bemessungsbetriebsstrom ....................................................
............................5 A......... 3 A .......... 1 A ...... 0,2 A...... 0,1 A
Minimale Kontaktbelastbarkeit .............. 1 mA bei AC/DC ≥ 10 V
S
: 9,6...150 V)
n
: 70...300 V)
n

Technical data

Data in tabular form
( )* = factory setting
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
Rated insulation voltage ................................................... 250 V
Rated impulse voltage/overvoltage category. ............... 4 kV / III
Pollution degree. .......................................................................3
Protective separation (reinforced insulation) between: ...............
.......................(A1, A2) - (U1/+, U2/-) - (11-12-14) - (21-22-24)
Voltage test acc. to IEC 61010-1 ...................................... 2.21 kV
Supply voltage U
S
VME421H-D-1 ..none (internally supplied by U
VME421H-D-2 ...none (internally supplied by U
Power consumption . ........................................................≤ 6 VA
Measuring circuit
Measuring range (r.m.s.)
VME421H-D-1 .......................................... . AC / DC 0...150 V
VME421H-D-2 ............................................ AC / DC 0...300 V
Rated frequency f
............................................ DC, 15...460 Hz
n
Frequency range ......................................................10...500 Hz
Switching elements
Number of changeover contacts ........................... 2 x 1 (K1, K2)
Operating principle ..................... N/C operation / N/O operation
K2 ......................................... Err, < U, > U, < Hz, > Hz, S.AL
................................ (undervoltage < U: N/C operation n.c.)*
K1 ..........................................Err, < U, > U, < Hz, > Hz, S.AL
.................................. (overvoltage > U: N/O operation n.o.)*
Electrical endurance .........................10000 switching operations
Contact data acc. to IEC 60947-5-1
Utilisation category ...............................................................
........................ AC 13..... AC 14 ..... DC-12 .... DC-12..... DC-12
Rated operational voltage .....................................................
........................ 230 V..... 230 V ........ 24 V ..... 110 V..... 220 V
Rated operational current. .....................................................
............................5 A......... 3 A .......... 1 A ...... 0.2 A...... 0.1 A
Minimum contact rating ..........................1 mA at AC/DC ≥ 10 V
VME421H_D00141_00_Q_DEEN/12.2019
LINETRAXX® VME421H
: 9,6...150 V)
n
: 70...300 V)
n
7