5.9 Humidity Control
The humidity control is an adjustable switch that closes
when the relative humidity of the air in which it is located
rises to the dial set point. It opens when the RH drops 4
to 6% below the set point.
5.10 Defrost Thermostat & Timer
The defrost thermostat is attached to the refrigerant
suction tube between the accumulator and compressor.
If the low side refrigerant temperature drops due to
excessive frost formation on the evaporator coil, the
thermostat opens. The compressor is then cycled off
and on by the defrost timer. The blower will continue to
run, causing air to flow through the evaporator coil and
melt the ice when the compressor is off. When the air
temperature and/or humidity increase, the evaporator
temperature will rise and the thermostat will close to end
the defrost cycle.
To improve performance in low temperatures, see Sec.
3.3 for defrost timer adjustment.
Toll-Free -800-
Figure 4: Electrical Schematic of HI-E Dry 195
8
5.11 Condensate Pump
Condensate is automatically pumped when the water
level in the pump's reservoir rises to close the float
switch.
If the pump is unable to empty its reservoir due to a
pump failure or blocked condensate hose, a pump safety
float switch is triggered before the reservoir overflows.
The switch turns off the compressor via its relay.
To replace the condensate pump:
. Unplug the unit & remove the front cover.
2. Disconnect the 2 hoses from the pump.
3. Cut the pump lead wires near the old pump.
4. Remove the 2 nuts from the unit side that hold the
pump to the side.
5. Attach the new pump with 2 nuts.
6. Connect the new pump wiring.
7. Connect the hoses to the new pump. Carefully
route the hoses so they do not contact the copper
refrigerant lines or the compressor shell.