ADELSYSTEM CBI60 Gebruiksaanwijzing - Pagina 4

Blader online of download pdf Gebruiksaanwijzing voor {categorie_naam} ADELSYSTEM CBI60. ADELSYSTEM CBI60 5 pagina's. Dc ups

Fig. 3 –Connection to DC Ups
Fig. 4 –Connection RTConn cable
For the ADELBus connection, please connect the cable RTConn to AUX1
on the device as shown in Fig.4 and connect the other side of the cable
to the CAN terminals L (Brown) and H (White) of the CBI60, with a line
termination (LT) resistor 120 Ohm, present inside the cable kit.

Ethernet Configuration

Configuration of the Ethernet interface by HTTP server via the Web
browser:
Connect HTTP server for the first time
Connect the device to the network with a standard CAT5e or better LAN
cable plugged into the Aux4 connector (RJ45) on the bottom of the unit,
as shown in section 4.3. The CBI60 is factory-configured to operate with
a fixed IP address (192.168.1.100) on the standard HTTP port (number
80).
A different static IP address can be assigned to the CBI60 or a dynamic
IP address can be assigned using the DHCP protocol. The network
configuration can be carried out using the internal webserver. Type the
IP address of the CBI60 into any browser's address bar (as an example
"192.168.1.100") then the login page appears requesting the username
and the password.
To access the internal webserver, at the login page, the following
credentials must be used:
Username: admin
Password: password
Note: after 20 minutes of inacticity the login credentials must be entered
again.
Customizing the ethernet interface and services
Select "Configuration" and then "Network" to display the following groups
of parameters and other information:
Account
Generic configuration
TCP/IP Configuration
HTTP(s) Configuration
SNMP
Via Luigi Barchi 9/B – Reggio Emilia 42124 – Italy
Tel. +39 0522 345518 – Fax +39 0522 345551 –
Account:
The Account group (Fig. 6) allows the customization of the data for the
HTTP server login page. Any changes must be confirmed with the
confirm button at the bottom of the page.
Fig. 6 – Account settings
Generic and TCP/IP Configuration
Fig. 7 shows the TCP/IP Configuration group with parameter default
values. They allow unique identification of the unit in the network.
Fig. 7 – IP settings
If "Dynamic (DHCP)" is selected, the IP address is automatically
assigned by a DHCP server, that must be active on the network; in this
case the System IP, Subnet Mask and Gateway textboxes show the
assigned values and are not editable.
The CBI60 supports access using the Virtual LAN protocol. In the case
"VLAN ID" checkbox is not selected the CBI60 will not operate in the
VLAN. If "VLAN ID" checkbox is selected then a "VLAN ID" textbox will
appear and should be populated with an ID in the range 1 to 4094,
matching the one of the VLAN the unit is operating in.
Any changes must be confirmed with the confirm button at the bottom of
the page.
HTTP(s)
The CBI60 supports HTTP and HTTPs protocols. If the client system
supports multicast DNS (mDNS) the device can be accessed by its name
(as set under Generic Configuration) followed by ".local".
HTTP Port allows redirecting the HTTP traffic to a port different than the
standard HTTP port 80. In that case, access to the HTTP server from a
browser must be made using the syntax http://ipaddress:portnumber.
As an example, if the IP address is 192.168.1.100 and the selected HTTP
port is 5678 then the following IP string should be entered in the browser
http://192.168.1.100:5678.
Secure HTTP (HTTPS) can also be selected, using an internal certificate
or a certificate provided by the customer.
Fig. 8 – HTTP(s) configuration
SNMP
The CBI60 can act as SNMP server. An ADELsystem MIB table file is
provided which consists of a list of parameters that can be remotely read,
or read-written through the SNMP protocol. Each parameter (OID) is
mapped one-to-one to a Modbus RTU holding register. Refer to the
document "Adelsystem parameter table" for the description of each
www.adelsystem.com
Instruction Manual CBI60_4
Page 4