ADEMCO 4110DL Handleiding voor installatie-instructies - Pagina 6
Blader online of download pdf Handleiding voor installatie-instructies voor {categorie_naam} ADEMCO 4110DL. ADEMCO 4110DL 16 pagina's.
Section 1. GENERAL DESCRIPTION
The 4110DL is a microprocessor-based state-of-the-art security controls intended for wired applications. The
Control Panel supports up to 6 hardwired zones and can be programmed either through the keypad or
remotely using ADEMCO's V-LINK downloading software.
––––––––––––––––––––––––––––––––––– FEATURES ––––––––––––––––––––––––––––––––––––
Zones Supported
•
6
hardwire
zones,
characteristics:
◊
EOLR supervision supporting N.O. or N.C.
sensors.
◊
300-500 msec normal response.
◊
Zone 3 programmable for Fast Response to
open (10mS).
Security Codes
•
1 master code for entire system (user 1)
•
3 secondary user codes (users 2-4)
Keypad Panic Keys
•
Provides 3 panic key functions
–––––––––––––––––––––––––––––––– SPECIFICATIONS ––––––––––––––––––––––––––––––––
4110DL CONTROL
1.
Physical:
12-1/2" W x 14-1/2" H x 3" D (318mm x 368mm x
76mm)
2.
Electrical:
VOLTAGE INPUT: 16.5VAC from plug-in 25VA
transformer, Ademco No. 1321/TF2 (in U.S.A.),
1321CN (in Canada)
RECHARGEABLE BACK-UP BATTERY: 12VDC,
4AH (Gel type).
CHARGING VOLTAGE : 13.8VDC.
ALARM SOUNDER: 12V, 2.0 Amp output
AUXILIARY POWER OUTPUT : 12VDC, 500mA
max. Interrupts for 4-wire smoke detector reset.
MAXIMUM ZONE RESISTANCE: Zones 1-8 =
300 ohms excluding EOLR
––––––––––––––––––––––––––––– COMPATIBLE DEVICES ––––––––––––––––––––––––––––
Remote Keypads (up to 4)
Model
4127, 6127
4137AD, 6137, 6128
5330 (Select for Vista)
Smoke Detectors (4-wire only)
Model
Type
1412
Ionization Products of Combustion
Detector
2412
Photoelectric Smoke Detector
2412TH
Photoelectric Smoke Detector)w/135º F
(57º C) Heat Detector)
having
the
following
Type
Fixed English
Fixed English Addressable
Alpha
Alarm Output
•
Provides a 12VDC, 2 AMP output (assumes a fully
charged battery is connected)
•
Steady output for Burglary/Panic, or pulsing
output for Fire
•
Output is current limited
Communication Formats
•
Ademco Low Speed (Standard or Expanded):
1400Hz ACK/KISSOFF.
•
Sescoa/Radionics (Standard or Expanded):
2300Hz ACK/KISSOFF.
•
Ademco Express :
DTMF, 1400/2300Hz ACK, 1400Hz KISSOFF.
•
Ademco Contact ID:
DTMF 1400/2300Hz ACK, 1400Hz KISSOFF.
In UL installations, maximum current
U L
draw from the Auxiliary Output and
the Alarm Output combined must not
exceed 500mA total.
FUSE :
Battery (3A) No. 90-12
LINE SEIZE: Double Pole
REGULATORY INFORMATION
Ringer Equivalence: 0.7B
FCC Registration No.: AC 398U-68192-AL-E
UL File No. S1632, Guide UXOU
Addressable keypads must be used in
the non-addressable mode (Device
Address 31), which is pre-set at the
IMPORTANT
factory. Do not set these keypads to
any other addresses.
Fire Supervisory Module
A77-71601 EOL Relay Module (supervises power for 4 -
wire fire zone).
Optional Keyswitch
4116 Keyswitch
-6-