Selecting the Options Using the DIP Switches
Programming and Setting up your HVAC
System
Review each pin setting explanation of each dip
switch function and choose your settings for
correct operations. Some functions may not
apply to your application.
** Push the reset button for 7 seconds whenever
there is a change the dip settings to reset the
CPU.
ON
HP < SYSTEM > OTHER
1
1
DF < HP > CONV
2
2
HC < TSTATS > HP
3
3
O < RV > B
4
4
OAS < STAGING > TIMER
5
5
OFF < 50% RULE > ON
6
6
OFF < SAS > ON
7
7
GAS < FAN > HYDRONIC
8
8
HP < SYSTEM > OTHER -
system you want to control. Select HP, if your
system is any type of Heat Pump. Select
OTHER, if your system is Hydronic/Electric
and/or Standard Cooling.
DF < HP > CONV -
If HP is selected type of
Heat Pump you want to control. Select DF
(Restricted Mode) locks out the compressor
during auxiliary heat operation. Select CONV
(Unrestricted Mode) if you wish to have the
compressor run during auxiliary heat operations.
HC < TSTATS > HP -
Heat/Cool thermostats, select HP for Heat
Pumps.
IMPORTANT NOTE: True thermostatic
staging is not available when using 2 Stage
compressors, it is advisable to use single stage
Heat/Cool or HP thermostats and allow the zone
panel to stage via the on-board timer.
O < RV > B -
Select the correct Reversing
Valve signal for your particular Heat Pump.
Choose "O" for any Heat Pump that energizes
the RV in the cooling mode. Choose "B" for any
Heat Pump that energizes the RV in heating
mode.
DEFAULT
OTHER
CONV
HC
O
TIMER
OFF
OFF
GAS
Type of HVAC
Select HC for regular
OAS < STAGING > TIMER -
want to delay auxiliary heat based on the
outside air temperature sensor. Select TIMER, if
you want to delay staging heat & cool based on
the adjustable on-board timer. NOTE: 'Y2' output
defaults to a 30 minute delay, when OAS is
chosen. An optional Outside Air Sensor (OAS) is
required to use the OAS feature.
OFF < 50% RULE > ON -
not want to inhibit Y2 and/or auxiliary heat
based on the total number of zones calling.
Select ON, if you want to inhibit Y2 and/or
auxiliary heat based on the total number of
zones calling. More than half the total zones
must be calling for the same mode of operation
(heat or cool), or the zone panel will not stage
up. The 50% rule will always dominate the
staging timer and thermostat demands unless
Emergency mode is active.
OFF < SAS > ON -
Select OFF, if you do not
want to use the supply air sensor for the Zone
Control system. Select ON, if you intend to use
an optional supply air sensor (SAS).
GAS < FAN > HYDRONIC -
fan mode is automatically set for you. There is
no need to move this switch when setting up for
operations.
Seven Built-in Timers for Safe & Reliable
Operation
** During set-up momentarily pressing the
RESET Button clears the built-in timers.
Pressing the RESET Button for 7 seconds will
reset the CPU.
* Start-up Delay Timer = 3 minutes-fixed
* Short Cycle Timer
* Change Over Timer = 4 minutes-fixed
* Opposing Call Timer = 20 minutes-fixed
* Staging Timer = OFF or 7-42 min.-Adj.
* Supply Air Limit Timer = 3 minutes-fixed
* Purge Delay Timer = 90 seconds-fixed
Startup Delay Timer - The panel will not
activate any cooling or heating operation until
the startup delay has expired.Momentarily
pressing the RESET Button clears the built-in
Select OAS, if you
Select OFF, if you do
NOTE: The indoor
= 3 minutes-fixed
Pre-Release 052917
052917