ADEMCO ADEMCO VISTA-15PSIA Snelle installatiehandleiding - Pagina 2
Blader online of download pdf Snelle installatiehandleiding voor {categorie_naam} ADEMCO ADEMCO VISTA-15PSIA. ADEMCO ADEMCO VISTA-15PSIA 2 pagina's. Ademco vista series security system
Ook voor ADEMCO ADEMCO VISTA-15PSIA: Snelle installatiehandleiding (2 pagina's), Handleiding voor programmering (17 pagina's), Gebruikershandleiding (20 pagina's), Snelle installatiehandleiding (2 pagina's), Beknopte handleiding (2 pagina's)
AC POWER AND BATTERY CONNECTION
AC POWER CONNECTION
AC POWER CONNECTION
TRANSFORMER
1.
CONNECT THE TRANSFORMER TO TERMINALS 1 AND 2.
SEE WIRE RUN CHART.
TRANSFORMER WIRE RUNS
USE CAUTION WHEN WIRING
Distance from control Wire Size
THE TRANSFORMER TO THE
Up to 50 feet
# 20
CONTROL TO GUARD AGAINST
BLOWING THE TRANSFORMER
50 - 100 feet
# 18
FUSE (THE FUSE IS
100 - 200 feet
# 16
NON-REPLACEABLE).
2.
AFTER ALL WIRING CONNECTIONS ARE COMPLETE, PLUG
TRANSFORMER INTO A 110VAC UNSWITCHED OUTLET (24HR)
USE 1361X10 TRANSFORMER INTERFACE WHEN POWER
LINE CARRIER DEVICES ARE BEING USED.
"AC LOSS" DISPLAYED IF VOLTAGE FALLS BELOW 16.5VAC.
BATTERY
1.
PLACE THE 12-VOLT BACKUP BATTERY IN THE CABINET.
2.
AFTER ALL CONNECTIONS TO THE CONTROL ARE MADE AND
AC POWER HAS BEEN APPLIED, CONNECT THE RED AND
BLACK FLYING LEADS TO THE BATTERY.
CONNECT ONLY AFTER AC POWER HAS BEEN APPLIED.
IMPORTANT: THE PANEL WILL NOT POWER UP INITIALLY ON
BATTERY POWER ONLY. YOU MUST PLUG THE TRANSFORMER
IN FIRST, AND THEN CONNECT THE BATTERY.
SOUNDER CONNECTION
CONNECT SOUNDER TO BELL TERMINALS 3 (+) AND 4 (-).
SOUNDER ACTIVATES UPON ALARM EVENT.
10.5–13.8VDC, 2A MAX. (600mA MAX. FOR UL USAGE,
INCLUDING AUX POWER) STEADY FOR BURGLARY/PANIC,
TEMPORAL PULSE SOUNDING FOR FIRE.
CAN USE ADEMCO No. 702 SIREN, OR 12V BELL.
A BATTERY MUST BE INSTALLED BECAUSE THE BATTERY
SUPPLIES THE CURRENT.
FOR SOUNDER SUPERVISION
EXTERNAL ALARM SOUNDER
IF BELL SUPERVISION IS
ENABLED (RED JUMPER ON
CONTROL BOARD IS CUT
TERM 4
AND
91 ENABLED)
2000 OHM
CONNECT A 2000 OHM
OBSERVE
EOL
POLARITY
RESISTOR ACROSS THE
TERM 5
RESISTOR
EXTERNAL SOUNDER AS
SHOWN BY THE DOTTED LINE.
DO NOT CONNECT THE RESISTOR AT THE ALARM OUTPUT TERMINALS THEMSELVES!
RF RECEIVERS & TRANSMITTERS
1.
SET RECEIVER DEVICE ADDRESS TO "00" (SET SWITCHES TO
THE RIGHT, "OFF" POSITION).
2.
MOUNT THE RECEIVER INSIDE THE CABINET OR REMOTELY
WITHIN A NOMINAL RANGE OF 200 FEET FROM TRANSMITTERS,
IN HIGH, CENTRALLY LOCATED AREA.
3.
CONNECT THE RECEIVER'S WIRE HARNESS TO THE CONTROL'S
ECP TERMINALS. SEE RECEIVER'S INSTRUCTIONS FOR
ANTENNA MOUNTING, ETC.
4.
INSTALL TRANSMITTERS ACCORDING TO THEIR INSTRUCTIONS.
WIRELESS ZONE NUMBERS
VISTA-20P:
VISTA-15P:
TRANSMITTER ZONES 9-48
TRANSMITTER ZONES 9-34
BUTTON ZONES 49-64
BUTTON ZONES 49-56
BATTERY FUSE
FOR
3A
REPLACEMENT,
USE SAME VALUE
BATTERY
(e.g. ADEMCO No. 90-12)
(12V, 4AH)
RED
BLACK
TO
1321
TERMINALS
(1321CN IN CANADA)
1 & 2
16.5VAC, 40VAC, CLASS 2
PLUG-IN TRANSFORMER
ECP AUX POWER OUTPUT
10.5-13.8VDC 600mA MAX.
(500mA MAX. FOR UL INSTALLATIONS)
AC
AC BELL
1
2
3
4219/4229
RF
EXPANDER
RECEIVER
MODULE
SENSORS
(USE 1K EOLR)
TOUCH
COMMUNICATION
SCREEN
DEVICE
KEYPAD
AR ME
D
RE AD
Y
ME SS
AG E
CONTROLLED
DEVICES
4204
RELAY
MODULE
BLACK
RED
GREEN
YELLOW
KEYPAD
KEYPADS AND ADDRESSABLE DEVICE CONNECTION
1.
CONNECT KEYPADS AND OTHER ADDRESSABLE DEVICES TO ECP TERMINALS 4-7.
(SEE "SETTING KEYPAD ADDRESS BOX TO SET KEYPAD ADDRESSES.)
TOUCH SCREEN KEYPADS MAY REQUIRE EXTERNAL
POWER SUPPLY DUE TO AUX POWER LIMITATIONS.
2.
SET EACH MODULE'S ADDRESS ACCORDINGLY:
DEVICE
ADDRESS
DEVICE
KEYPADS
16 - 23
5800TM
28 (PART. 1 ONLY)
4219, 4229
07 - 11
COMM DEVICE
03
4204
12 - 15
4286
04
RF RECIEVER
00
TOUCH SCREENS
01, 02, 05, 06
TRIGGER CONNECTOR
+
5
OPTIONAL
USED FOR 1361X10
TRANSFORMER
1361X10
CONNECTIONS AND FOR
AUX PWR
PROGRAM RELAY
ON-BOARD TRIGGERS.
OUTPUT
AS ZONE TYPE 54
(USE SA4120XM-1 CABLE)
TERMINALS
(FIRE ZONE RESET)
1 2 3 4
5 6
7 8
_
4
OR
CONTACT OPENS MOMENTARILY
UPON FIRE ALARM RESET
TO OUTPUT 17
PROGRAM OUTPUT 17 FOR
"OUT NORM LOW" = YES IN
79 MENU MODE AND AS ZONE
BLUE (DATA)
TYPE 54 IN
80 MENU MODE
MAX. CURRENT = 100 mA
PURPLE (COM)
(UP TO 16 DETECTORS
BLACK (SYNC)
PLUS EOL MODULE)
(+)
TO ZONE 2 8 TERM.
_
( )
RED JUMPER
CUT FOR BELL SUPERVISION. ALSO,
CONNECT 2000 OHM RESISTOR DIRECTLY
ACROSS SOUNDER AND ENABLE FIELD
91.
HARDWIRE ZONES
ECP DEVICES
`
GND
AUX
IN
OUT
Z1+
Z1
GND
Z2
Z3
GND
Z4
Z5
GND Z6
4
5
6
7
8
9
10
11
12
13
14
15
16
17
2000
2000
2000
2000
2000
2000
OHMS
OHMS
OHMS
OHMS
OHMS
OHMS
EOLR
EOLR
EOLR
EOLR
EOLR
EOLR
2-WIRE SMOKE
DETECTORS
(16 MAX) OR
STANDARD
2K EOLR
HARDWIRE ZONE CONNECTION
1.
OPEN CIRCUIT DEVICES CONNECT IN PARALLEL ACROSS
THE LOOP; FOR EOLR ZONES, CONNECT THE EOLR
ACROSS THE LOOP WIRES AT THE LAST DEVICE.
2.
CLOSED CIRCUIT DEVICES CONNECT IN SERIES IN THE
HIGH (+) SIDE OF THE LOOP; FOR EOLR ZONES, CONNECT
THE EOLR IN SERIES FOLLOWING THE LAST DEVICE.
EOLR NOTE:
IF THE EOLR IS NOT AT THE END OF THE LOOP, THE
ZONE IS NOT PROPERLY SUPERVISED AND THE SYSTEM
MAY NOT RESPOND TO AN "OPEN" ON THE ZONE.
UL NOTE:
FOR UL COMMERCIAL BURGLARY ALARM INSTALLATIONS,
USE EOLR ZONES.
DOUBLE-BALANCED ZONE
12
13
14
ZONE DOUBLING
TAMPER
2k
CONTACTS
2k
10
ZONE 2
TAMPER
2k
2k
CONTACTS
ZONE 10
2k
2k
ADDRESS
ZONE 3
ZONE 4
DO NOT USE DOUBLE-BALANCED ZONES
OR ZONE DOUBLING FOR FIRE ZONES.
4-WIRE SMOKE DETECTOR CONNECTIONS
RELAY
_
BLK
+
RED
EOL
POWER
N.O.
SUPERVISION
N.C.
RELAY MODULE
A77-716B.
USE N.O.
CONTACT,
VIOLET
WHICH CLOSES
+
_
WHEN POWER
IS APPLIED.
4-WIRE SMOKE
2000
OR COMBUSTION
DETECTOR
OHMS
EOLR
HEAT
DETECTOR
HANDSET
INCOMING
Z7
GND
Z8
TIP
RING
TIP
RING
GND
18
19
20
21
22
23
24
25
EARTH
GROUND
2000
2000
THIS CONTROL DOES NOT NORMALLY NEED AN EARTH GROUND. IF
OHMS
OHMS
DESIRED FOR ADDITIONAL PROTECTION, CONNECT TERMINAL 25 TO A
EOLR
EOLR
GOOD EARTH GROUND. EXAMPLES OF GOOD EARTH GROUNDS:
METAL COLD WATER PIPE: USE A NON-CORROSIVE METAL STRAP
(COPPER IS RECOMMENDED) FIRMLY SECURED TO THE PIPE TO WHICH
THE GROUND LEAD IS ELECTRICALLY CONNECTED AND SECURED.
AC POWER OUTLET GROUND: AVAILABLE FROM 3-PRONG, 120VAC
POWER OUTLETS ONLY. TO TEST THE INTEGRITY OF THE GROUND
TERMINAL, USE A 3-WIRE CIRCUIT TESTER WITH NEON LAMP
INDICATORS, SUCH AS THE UL LISTED IDEAL MODEL 61-035, OR
EQUIVALENT, AVAILABLE AT MOST ELECTRICAL SUPPLY STORES.
RING (GRAY)
PREMISES
TIP (BROWN)
PHONES
RING (RED)
1
2
3
4
RJ31X
5
TIP GREEN)
8
7
6
PHONE CONNECTION
1.
CONNECT PHONE LINE DIRECT
CONNECT CABLE WIRES TO
TERMINALS 21-24 AS SHOWN.
WIRE COLORS REPRESENT THE
COLORS OF THE CABLE TO THE
RJ31X JACK.
ZONE
PAIRS
2.
CONNECT INCOMING PHONE
11
LINE AND HANDSET WIRING TO
2 / 10
THE MAIN TERMINAL BLOCK
3 / 11
(VIA AN RJ31X JACK; CA38A IN
4 / 12
CANADA) AS SHOWN.
5 / 13
6 / 14
3k
7 / 15
8 / 16
6.2k
KEYSWITCH WIRING CONNECTIONS
1 2 3 4
5 6
7 8
TRIGGER CONNECTOR
4146 KEYSWITCH
STANDARD
(ARMED)
KEYPAD
RED
CABLE
YELLOW
(READY)
GREEN
WHITE
820
820
ohms
ohms
BLACK
RED
TAMPER
SWITCH (N. C.)
BROWN
BROWN
11
TYPICAL ZONE
LOCK
ON CONTROL
SWITCH (N. O.)
BOARD
BLUE
BLUE
10
2K OHM EOLR
EARTH GROUND CONNECTION
INCOMING
TELCO
SETTING KEYPAD ADDRESS
HOLD
DOWN
THREE
SECONDS
1
2
3
ARMED
OFF
AWAY
STAY
4
5
6
READY
MAX
TEST
BYPASS
7
8
9
INSTANT
CODE
CHIME
0
#
READY
1.
POWER UP THE KEYPAD. WITHIN 60 SECONDS OF
POWER-UP, PRESS AND HOLD DOWN THE [1] & [3] KEYS
AT THE SAME TIME FOR 3 SECONDS.
2.
ENTER THE PROPER "TENS" DIGIT OF THE KEYPAD'S
ADDRESS, THEN ENTER THE PROPER "ONES" DIGIT
OF THE KEYPAD'S ADDRESS.
NOTE: FIRST KEYPAD IS ADDRESS 16
3.
PRESS [ ] TO SAVE THE DISPLAYED ADDRESS AND
EXIT ADDRESS MODE.
V15P_V20P_quick-guide