Automated Logic S6104 Technische instructies - Pagina 10
Blader online of download pdf Technische instructies voor {categorie_naam} Automated Logic S6104. Automated Logic S6104 16 pagina's.
- 1. Table of Contents
- 2. Using the S6104
- 3. Specifications
- 4. Mounting
- 5. Addressing
- 6. Power Wiring
- 7. Network Communications
- 7. Using the S6104 on an ARC156 Segment
- 7. Using the S6104 on a Legacy Cmnet
- 7. Connecting the S6104 to the Network
- 7. Communicating through the Logistat Port Using Supervision
- 7. Communicating through the Access Port Using Supervision
- 8. Inputs
- 8. Logistat Wiring
Universal Input
Mode Select
0-5VDC
Thermistor/
0-20mA
dry-contact
Figure 10. Universal Input Mode Select
5. Turn the S6104's power switch on.
6. For each input, enter the point identifiers.
• In WebCTRL, enter the point number
and the point type on the Properties
page. For linear inputs, set the
minimum value and maximum value to
scale the point to engineering units.
• In SuperVision, enter the channel
number, offset, and gain using the
Configure Points or Point Help feature.
Valid channel numbers are listed in
"Channel Numbers in SuperVision" on
page 13.
7. To verify each input's operation, have
each sensor create a known value and
compare it to the condition reported on
the FB's Properties page in WebCTRL or
Status page in SuperVision.
LogiStat Wiring
The S6104's LogiStat Port provides the
connection for a LogiStat room sensor (see
Figure 1 on page 2). The Input Select jumper
must be set to the LogiStat position when
using a LogiStat or LogiStat Plus. This allows
the S6104 to obtain analog temperature
readings from the LogiStat through pin 2
(Temp) of the LogiStat Port. The LogiStat Plus
also provides the slidepot position and TLO
inputs through pin 3 (Sw). The LogiStat Pro
provides temperature, setpoint adjust, and
TLO inputs through serial communications.
See Table 4 for the wiring restrictions for the
S6104.
Revised 7/30/02 • S6104
Grip
here
Refer to the section "Writing GFBs for the
S6104" on page 12 for more information
about using a LogiStat sensor.
1. Be sure the S6104's power is off before
wiring a LogiStat to the LogiStat Port.
2. If using a LogiStat or LogiStat Plus, set the
Input Select jumper to LogiStat (see Figure
11).
NOTE Setting the jumper to LogiStat
disables universal inputs 9 and 10.
IN9/IN10
LogiStat
Figure 11. Input Select set to LogiStat
If using a LogiStat Pro, set the Input Select
jumper to IN9/IN10 to make the inputs
available for use.
3. If using a LogiStat Pro, set the Port Select
jumper to LogiStat; this enables
communications through the LogiStat
port.
NOTE The S6104 must be on an ARC156
network segment using a LogiStat Pro.
10
© 2002 Automated Logic Corporation
Open Energy
Management Equipment
R
88FO
E143900
Input Select
TYPE: 006104
IN9/
LogiStat
IN10