Common Alarms
Custom Translation
Tables
ZN551 Control Module • Rev. 3/17/2005
Ack Required for Off-Normal,
Fault, and Normal
Recipient List
Recipients
Recipient Description
Recipient Type
Recipient Device Object
Identifier
Process Identifier
Issue Confirmed
Notifications
On these pages, you can change the following control module alarm
properties:
•
BACnet alarm object properties
•
Enable/disable
•
Delays
NOTE To set up alarm actions for control module generated alarms, see
Setting up alarm actions in WebCTRL Help.
Module Generated Alarm
Description
Events
Alarm Category and Alarm
Template
Enable
Notification Class
On the Custom Translation Table pages, you can edit the tables used to
translate raw sensor data to engineering units for inputs associated with
Non-Linear, Custom Table sensor/actuator types.
15
Requires a control module acknowledgement for each
message type. Normally not required.
TIP To require operator acknowledgement for an Alarm
or Return-to-normal message (stored in the WebCTRL
database) change the acknowledgement settings on
WebCTRL's Alarm > Enable/Disable tab for an alarm
source or an alarm category.
The first row in this list is the WebCTRL Server. Do not
delete this row. Click Add if you want other BACnet
devices to receive alarms.
Name that appears in the Recipients table.
Use Address (static binding) only for third-party BACnet
device recipients that do not support dynamic binding.
Type the Device Instance from SiteBuilder (or from the
network administrator for third-party devices) in the #
field.
Change for third-party devices that use a BACnet Process
Identifier other than 1. WebCTRL processes alarms for
any 32-bit Process Identifier.
Select to have a device continue sending an alarm
message until it receives delivery confirmation from the
recipient.
Short message shown on WebCTRL's Alarm page or in an
alarm action when this type of alarm is generated.
See Customizing alarms in WebCTRL Help.
Clear these checkboxes to disable Alarm or Return to
normal messages of this type from this control module.
Do not change this field.