Emergi-Lite DLM-2 Series Handmatig
Blader online of download pdf Handmatig voor {categorie_naam} Emergi-Lite DLM-2 Series. Emergi-Lite DLM-2 Series 2 pagina's. Decorative emergency lighting unit
DLM-2 Series
Decorative Emergency Lighting Unit
Disconnect Power before Installation.
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always
be followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1. All servicing should be performed by qualified service personnel.
2. All unused wires must be insulated to prevent shorting.
3. Do not use outdoors.
4. Do not let power supply cords touch hot surfaces.
5. Do not mount near gas or electric heaters.
6. Use caution when handling batteries. Battery acid can cause burns to the skin
and eyes. If acid is spilled on the skin or eyes, flush affected area with fresh
water and contact a physician immediately.
7. Avoid possible shorting.
8. Equipment should be mounted in locations and at heights where it will not
readily be subjected to tampering by unauthorized personnel.
9. The use of accessory equipment not recommended by the manufacturer may
cause an unsafe condition.
10. Do not use this equipment for other than intended use.
11. When relamping, only use lamps specified in the fixture.
12. Allow battery to charge for 24 hours before first use.
SAVE THESE INSTRUCTIONS
Installation Instructions
Install product no higher than the maximum
IMPORTANT:
mounting height of 7 feet 6 inches from the
floor.
1. Turn of AC power.
2. Using a flat head screwdriver, insert the blade into the slot and gently
pry off the back plate (see figure 2).
Wall and Ceiling Mount
1. Remove the appropriate knockouts in the back plate to mount to a
standard junction box.
2. Feed unit wires through the center hole of the back plate.
3. Make the proper connections (see figure 4):
a. For 120VAC, connect the black wire (120Vac) and white wire
(neutral) to the building utility.
b. For 277 VAC, connect the orange wire (277Vac) and white wire
(neutral) to the building utility.
c. Feed wires back into the junction box.
4. Mount and secure the back plate to the junction box.
5. Connect the red wire to the battery positive terminal (see figure 3).
6. Snap housing to back plate.
7. Restore power and press the test button.
Emergi-Lite®
Tel: (888) 552-6467
®
WARNING:
Risk of Shock.
Figure 1
Parts list
1. Lens
2. Lamp bulbs(2)
3. Housing
4. Lamp holder
5. PCBA board
Figure 2
Figure 3
Fax: (800) 316-4515
www.emergi-lite.com
DLM-2 Series
6. Power connector
7. Battery
8. Battery bracket
9. Back plate
Red battery
lead
Battery
10/16 750.1329 Rev. B
1/2