Exit panel installation (Figure 1)
1. Remove the exit panel form its carton, do not remove the protective
sleeve until the installation is complete.
2. Partially remove the protective sleeve at the top of the exit panel.
Push the exit panel, with the clips, into the slot in the trim plate
assembly until it snaps. Gently try to pull out the panel to ensure that
it is engaged in the trim plate assembly. Remove the protective
sleeve.
3. Energize AC circuit. Legend and green pilot indicator (self-powered
models), will illuminate.
Important: the Exit panel can only be removed by lowering the trim plate
and pushing on the end clip located on the opposite side of the test
switch with a screwdriver.
Self Powered models
Manual testing (Figure 6)
Press test switch. Legend will flicker then will remain lit. On release,
external green LED will illuminate, and automatic charger will restore
battery to full charge.
Automatic testing and diagnostics (optional)
The models with the automatic testing and diagnostic option include a
micro-controller which tests the unit on a monthly basis and identifies as
well displays failures of the electrical components: battery, charger cir-
cuit, LED lamps.
Self-test
The self-test is performed every 30 days for 30 seconds, every 60 days
for 30 minutes, and annually for 90 minutes.
Diagnostic function (Figure 6)
The diagnostic function uses the pilot light LED indicator. Service is
required if the green LED changes color to red indicating that an alarm
condition is detected.
Status
Pilot light
Steady
Green
Blinking
Green
Steady on
Red
Red
One Blink
Two Blinks
Red
Four Blinks
Red
Maintenance
None required. Models equipped with batteries: if AC supply is to be dis-
connected for 2 months or more, the battery must be disconnected (Self-
Powered Models only).
Note — For safety reasons Nickel Cadmium batteries are shipped dis-
charged. The unites may require 10 minutes of connection to AC supply
before start-up test procedure, and two to seven days to reach full
charge.
Emergi-Lite
Tel: (888) 552-6467
Diagnostic
Normal (AC On)
Auto Test
Battery Disconnect
Battery Failure
Charger Failure
LED Lamp Failure
Fax: (800) 316-4515
Prestige Series - Edge-Lit LED Exit Series
Red + DC
Blue - DC
DC wires
for remote
DC supply
Figure 3
(Regular models)
(Optional)
Red 347VAC
Orange 277VAC
Black 120VAC
White neutral
Figure 4
(Models with diagnostic feature)
Figure 5
AC Pilot light / Test switch
Diagnostic light (optional)
Trim plate
Figure 6
www.emergi-lite.com
Purple AC
White neutral
Back box
LED Strip
DC wires for
Fire alarm input
Red + Fire Alarm
Blue - Fire Alarm
Back box
Transformer
LED Strip
07/09 750.1436 Rev. A