15. Calibration is finished.
You can select and copy the
text in the box if you want a
copy of the calibration
information.
Click Finish.
Below is an example of the calibration status box text.
Calibration is finished. Click the Finish button to exit.
Click Next to continue.
Offset calibrations stored successfully.
--------------------------------
Voltage - Phase C Offset Calibration: 0
Voltage - Phase B Offset Calibration: 0
Voltage - Phase A Offset Calibration: 0
Current - Phase C Offset Calibration: 0
Current - Phase B Offset Calibration: 0
Current - Phase A Offset Calibration: -1
--------------------------
Click Next to continue.
Current for phase A, B, and C are: 0A, 0A, and 0A.
Reading current...
Click Next.
Set the load to the high point and enter the current in the box above.
---------------------------------
Click Next to continue.
Current for phase A, B, and C are: 0.1A, 0A, and 0A.
Reading current ...
Click Next.
Set the load to the low point and enter the curent in the box above.
--------------------------
Click Next to continue.
Slope calibrations stored successfully.
Current - Phase C Slope Calibration: -29
Current - Phase C Delta Slope Calibration: 0
Current - Phase B Slope Calibration: 55
17 of 18