APPENDIX A
TROUBLESHOOTING
Problem: No power to AirCycler® g2
Check common wire connection. "C" must be connected to "C" on the furnace.
Problem: EXH icon is flashing
If the EXH icon is flashing it is indicating that the FanConnect™ switch has been on for more than four hours or has lost
connection with the AirCycler® g2 controller.
Problem: Furnace fan is running constantly
Make sure the thermostat FAN switch is set to AUTO and not ON
Problem: Central fan does not shut off when AirCycler® g2 is removed from base (when thermostat fan switch is on)
Check wiring - "G" wire from thermostat should be wired to "Gt" on AirCycler® g2. "Gf" on AirCycler® g2 should be
connected to "G" on furnace.
Problem: Blank Display on the AirCycler® g2
Confirm:
1. The furnace has power
2. The thermostat is operational
3. The furnace will call for heat from the thermostat
4. The fan operates with a fan only signal from the thermostat
5. The furnace is providing 24 VAC to the AirCycler® g2
6. Verify wiring conforms to wiring diagram
7. Make sure cover is firmly seated on the base
Problem: AirCycler® g2 turns furnace fan on and off, but the motorized damper does not cycle.
Confirm:
1. The AirCycler® g2 is providing a 24 VAC signal to the motorized damper
2. The 24 VAC motorized damper is operational by powering directly with a 24 VAC signal
3. There is continuity in the wiring between the damper and the AirCycler® g2
4. Confirm damper power switch is in up or automatic position
Problem: A/C turns on during fan cycling calls
Confirm:
1. Wiring conforms to wiring diagram
2. The G wire is properly connected
3. The G wire needs to be interrupted by the AirCycler® g2
4. Do not run the G wire in parallel
Problem: The AirCycler® G2 does not detect the optional FanConnect™ switch
Confirm:
1. Verify the FanConnect™ has power and is in the OFF position
TIPS
1. Make sure the FanConnect™ switch is in the OFF position when the AirCycler® g2 is first powered on.
2. Setup is easier to start without the battery installed. The battery is only used for the real time clock. If you
are not using the operating hours setting, the battery is not needed.
3. To set the AirCycler® g2 to "Inverse Slave Mode" - run the exhaust fan whenever the central fan is not running - enter
Calculated Flow setup. Set Measured Supply Air Flow, Measured Exhaust Air Flow, and Required Constant Airflow to the
same levels. For example, set all to 60 CFM.