HID EdgePlus Snelle installatiehandleiding - Pagina 10

Blader online of download pdf Snelle installatiehandleiding voor {categorie_naam} HID EdgePlus. HID EdgePlus 14 pagina's.

EdgeReader and EdgePlus Installation
Update System
Update System allows the user to update the firmware on the Edge device. During a download the
Edge device image flashes between grey and yellow. When a download completes the image color
changes to green for success or red for failure. If the download fails, a tool tip with the error status code
may be viewed by hovering the mouse over the image.
Note: Depending on the system, it may take several minutes to completely download.
Network Defaults Jumper
The Network Defaults Jumper requires that someone with physical access to the Edge device place
a jumper over the P65 header prior to the rebooting the device. The Edge device reconfigures its
network settings to the factory defaults when the jumper is on the header. From this point,
configuration (or re-configuration) will proceed normally.
Use the Network Defaults Jumper to correct potential errors in an Edge device network configuration.
CAUTION: Upon rebooting the Edge device (with a jumper in place,) all network configuration
information will be overwritten.
1. Remove the jumper from Tamper header
2. Place the same jumper over the left two pins of the P65 header (as shown in Figure 1 Network
Defaults Jumper).
3. Reboot the Edge device to change all of the configuration settings back to the factory defaults.
4. After the LED turns amber, remove the jumper from the P65 header, returning it to the tamper
header. Upon removing the jumper it takes approximately 60 seconds for the Edge device to
reset. Once the reset is complete, the LED will return to green.
5. Configure the Edge device for your installation parameters.
April 2007
Figure 1 Network Defaults Jumper
© 2007 HID Global Corporation. All rights reserved.
Part No. 82000-901
Page 10 of 14