1.2 OPERATION EXAMPLES CONT'D
0
CENTRAL FAN
DAMPER
OPEN
15 MINUTES OF
HEATING/COOLING
15 MIN x 90 CFM
=
1,350 CF
After regular heating/cooling cycles, ventilation requirements for the hour were not met. At the end of the hour the
AirCycler® g2 forced on the bathroom exhaust fan, via the FanConnect™ switch, to reach required ventilation.
0
CENTRAL FAN
DAMPER
OPEN
10 MINUTES OF
HEATING/COOLING
10 MIN x 90 CFM
=
After regular heating/cooling cycles and manual occupant use of bathroom exhaust fan, ventilation requirements for the
ONE HOUR VENTILATION (MINUTES)
VENTILATION REQUIREMENTS = 30 CFM CONTINUOUS OR 1,800 CF/HR
NORMAL CENTRAL FAN OPERATION + AIRCYCLER® G2 FORCED EXHAUST
15
DAMPER
CLOSED
= NORMAL OPERATION
NORMAL CENTRAL FAN OPERATION + OCCUPANT EXHAUST USE
15
DAMPER
CLOSED
900 CF
= NORMAL OPERATION
hour were met. No need for additional ventilation forced by AirCycler® g2.
30
= OCCUPANT ACTIVITY/AIRCYCLER® G2 FORCED EXHAUST
30
EXHAUST FAN
= OCCUPANT ACTIVITY/AIRCYCLER® G2 FORCED EXHAUST
9
45
EXHAUST FAN
DAMPER
OPEN
FORCED ON
BY G2 VIA
FANCONNECT
FOR 7.5 MIN
7.5 MIN x 60 CFM =
450 CF +
1,350 CF = 1,800 CF
VENTILATION
REQUIREMENT
COMPLETE
45
DAMPER
DAMPER
OPEN
CLOSED
15 MIN OF
BATHROOM USE
(MANUAL USE
OF FANCONNECT
SWITCH)
15 MIN x 60 CFM =
900 CF
900 CF + 900 CF =
1,800 CF
VENTILATION
REQUIREMENT
COMPLETE
60
DAMPER
CLOSED
450 CF
60
AC DOC 8.5
REV 7/2020