Control Menu Layout for VF Series
Normal Operation Display
Main Menu
Power Settings
Frequency Settings
Timer Settings
I/O Interface
Security
Language
Diagnostics
Defaults
Normal Display Message Priority:
Status Line Message
CFR Set Point
Amplitude
Frequency
The normal operating display shows the status of the control with regard to input signals and control settings. They
are listed from highest to lowest in priority. The highest priority message takes precedence over the other messages.
Stop/Run - The 1/0 button has been pushed to disable control operation.
Override - The 1/0 button has been pushed and held so the control feeds while ignoring the "Sensor" or "Run" inputs.
Run Input - The run jumper has not been not made.
Parts Sens - The parts sensor and control logic is telling the control to stay off.
Empty/jam - Empty bowl timer has timed out because parts did not pass by the parts sensor to reset the timer.
Analog - An external signal is in control of the speed input.
Low - Low Speed used when 2 speed has been selected and the sensor is not made.
Zero Speed - The output is off because the output is set to 0.0%.
Run – The feeder is running normally.
Run/CFR – Constant Feed Rate sensor is regulating the feed rate (Autotune®).
Press and hold 'Enter' key to enter the program menu or get to the security
menu. Then use the "Enter" key to move right from Main Menu to Sub Menu to
the Adjustable Setting. Use the "Back" key to move left.
Sub Menu
Amplitude
Max Amplitude
Min Amplitude
Soft Start Time
Amplitude Source
Amplitude Set-Point
CFR Positive Gain
CFR Negative Gain
Current Limit
Frequency
Max Frequency
Min Frequency
Frequency Mode
Auto Scan
Resonate Threshold Level [ 15.0 Default ]
Auto Track Dead Band
On Delay
Off Delay
Empty Bowl Timer
Sensor Polarity
Run Mode
Run Input
Empty Bowl
Aux Output Mode
Keypad Lock
Security Code
Pick Language
Board/Load Current
Accelerometer
AC Volts
Analog 4-20 mA, 0-10 V
Temp, Temp, PS Volts
Software, Software Vers.
Restore Settings 1
Restore Settings 2
Restore Settings 3
Save Settings 1
Save Settings 2
Save Settings 3
Factory Reset
Run/CFR
CFR=024.5
A= 40.0%
F= 60.0Hz
Adjustable Setting
[
0.0 to 100.0 ] %
[ 100.0 to 20.0 ] %
[
0.0 to 95.0 ] %
[
0.0 to 10.0 ] Seconds (0.5 Default)
[ Auto Tracking Manual, 0-10V, 4-20mA ]
[
0.0 to 1250 ] vibration level
[ 7 Default ]
[ 12 Default ]
[ 9.5 VF-9, (3.5 VF-3), (12.5, VF-12), (18.0, VF-18) Default] Amps
[
5.0 to 180.0 ] Hz (60.0 Hertz Default)
[ 15.0 to 180.0 ] Hz (140.0 Hertz Default)
[
5.0 to 170.0 ] Hz (45.0 Hertz Default)
[ Auto Tracking, Manual ]
[ Press ENTER to perform an automatic frequency scan ]
[ 15 Default ]
[
0.0 to 20.0 ] Seconds (0.5 Default)
[
0.0 to 20.0 ] Seconds (0.5 Default)
[
5 to
255 ] Seconds (10 Default)
[ Inverted, Normal ]
[ Normal, Always On, 2-Speed, High/Low ]
[ Normal, Disable ] Run Input can be ignored.
[ Normal, Stop ]
[ Normal, Inverted, Alarm, Inv Alarm, Air Jet ]
[ Unlocked, Amplitude Only, Locked ]
[ 00.0 to 99.9 ]
[
English, Spanish, French, German, Czech, Dutch, Italian, Polish,
Portuguese, Swedish, Turkish
[ data, data ] Board, Amps
[ data ] signal amplitude
[ data ] Volts
[data, data] mA, Volts
[ data ], [ data ] °C, [ data ] Volts → Self Test1/factory reset (factory test only)
[ data ] Power, [ data ] Display
[ 'Enter' Restores User Settings 1 ]
[ 'Enter' Restores User Settings 2 ]
[ 'Enter' Restores User Settings 3 ]
[ 'Enter' Saves User Settings 1 ]
[ 'Enter' Saves User Settings 2 ]
[ 'Enter' Saves User Settings 3]
[ 'Enter' Resets Control to Factory Default Settings (Shown in bold) ]
R=1
Run Input: 1= on /closed & 0= off/open
S=1
Sensor Input: 1= on /closed & 0= off/open
O=1
Output to vibratory feeder: 1= on & 0= off
A=1
Aux Output: 1= on & 0= off
]
ADI VF Menu v2_05.docx 10/13/22 Page 3