Automation Direct DURApulse GS4 Snelstarthandleiding - Pagina 4

Blader online of download pdf Snelstarthandleiding voor {categorie_naam} Automation Direct DURApulse GS4. Automation Direct DURApulse GS4 9 pagina's. Ac drive

Automation Direct DURApulse GS4 Snelstarthandleiding
DURApulse GS4 AC Drive Quick-Start Guide
DURA
GS4 Quick-Start Parameter Settings #3 – Enhancements
pulse
Parameter
Description
Settings
1
P1.09
S-curve Accel Time 1
P1.15=0: 0.00~25.00 sec
P1.15=1: 0.0~250.0 sec
2
P1.10
S-curve Decel Time 1
3
P1.13
Jog Acceleration Time
P1.15=0: 0.00~600.00 sec
P1.15=1: 0.0~6000.0 sec
4
P1.14
Jog Deceleration Time
5
P5.00
Jog Frequency
0.00~600.00 Hz
6
P1.19
Skip Frequency 1 Upper Limit
0.00~600.00 Hz
7
P1.20
Skip Frequency 1 Lower Limit
8
P1.25
DC Injection Current Level
0~100%
9
P1.26
DC Injection Time During Start-up
0.0~60.0 sec
10
P1.27
DC Injection Time During Stopping
Start-Point for DC Injection During
11
P1.28
0.00~600.00 Hz
Stopping
0: General Purpose
1: High Starting Torque (TQR)
2: Fans and Pumps
12
P2.00
Volts/Hertz Settings
3: Custom
4: 1.5 Power Curve *
5: Square Curve *
13
P2.01
Slip Compensation Gain
0.00~10.00
14
P2.25
Slip Compensation Filter
0.001~10.000 sec
15
P2.02
Torque Compensation Gain
0~10
16
P2.03
Torque Compensation Filter
0.001~10.000 sec
17
P2.10
PWM Carrier Frequency
2~15 kHz
0: V/Hz Open Loop Control
18
P2.11
Control Mode
1: SVC Sensorless
0: Standby
19
P2.18
Zero Speed Select
1: Zero Hold
2: Fmin (Min Hz Output)
20
P6.25
Upper Limit of Output Frequency
0.00~600.00 Hz
0: Disable
21
P2.23
Automatic Energy-Saving Operation
1: Enable
22
P2.24
Power Saving Gain
10~1000%
23
P2.26
Slip Deviation Level
0.0~100.0
24
P2.27
Slip Deviation Detection time
0.0~10.0
0: Warn and continue OP
1: Warn and Ramp to Stop
25
P2.28
Slip Deviation Treatment
2: Warn and Coast to stop
3: No Warn
♦ The diamond bullet symbol indicates a parameter that can be set during operation.
* Energy Saving Power Curves For Fans & Pumps. (P2.00 settings 4 & 5)
GS4_QSP_1edRevC 07/02/2021
DURA
GS4 Quick-Start Parameter Settings #4 – Protection
pulse
Default
User
Parameter
Description
0.20
1
P6.04
Auto Restart after Fault
0.20
2
P6.05
Reset Time for Auto Restart after fault
10.00
10.00
3
P6.06
Base Block Speed Search after Fault (oc,ov,bb)
6.0
0.00
0.00
4
P6.09
Fwd/Rev Direction Inhibit
0
0.0
0.0
0.00
5
P6.13
Auto Adjustable Accel/Decel
0
6
P6.14
Over-torque Detection Mode (OT1)
0. 00 (V/Hz mode)
1. 00 (Vector mode)
0.100
7
P6.15
Over-torque Detection Level (OT1)
0
8
P6.16
Over-torque Detection Time (OT1)
0.5
9
P6.26
Lower Limit of Output Frequency
model specific;
10
P6.28
Dynamic Braking Voltage Level *
refer to param.
details
11
P6.29
Line Start Lockout
0
0
12
P6.31
Cooling Fan Control
600.00
13
P6.32
PWM Fan Speed
0
100
14
P6.45
Output Phase Loss (OPhL) Detection Selection
0.0
1.0
15
P6.46
Output Phase Loss Detection time
16
P6.47
Output Phase Loss Current Detection Level
0
17
P6.49
Input Phase Loss Treatment
18
P6.69
Input Phase Loss Detection Time
19
P6.70
Input Phase Loss Ripple Detection
20
P6.50
GFF Detect Current Level (% of INV I-Rated)
21
P6.51
GFF Low Pass Filter Gain
22
♦ P6.71
STO Alarm Latch
♦ The diamond bullet symbol indicates a parameter that can be set during operation.
* Valid only for 230V models below 30hp and 460V models below 40hp. (P6.28)
Settings
Default User
Parameter
0~10
0
0.0~6000.0 sec
60.0
0: Disable
1
P7.00
1: Speed search starts with current
speed reference
0
2: Speed search starts with minimum
output frequency
0: Enable Fwd/Rev
2
P4.00
1: Disable Reverse Operation
0
2: Disable Forward Operation
3
P4.01
0: Linear Accel/Decel
1: Auto Accel, Linear Decel
4
P4.02
2: Linear Accel, Auto Decel
5
P4.03
3: Auto Accel, Auto Decel
0
4: Auto Accel/Decel Stall Prevention
6
P4.04
(limited by P1.01~P1.08 and
7
P4.05
P1.13~P1.14)
8
P4.06
0: Disable
1: Enable during at speed
9
P7.03
2: Enable during at speed and Stop
0
10
P7.04
3: Enable during OP
11
P7.13
4: Enable during OP and Stop
12
P7.14
10~200%
120
13
P7.15
0.1~60.0 sec
0.1
14
P7.18
0.00~600.00 Hz
0.00
15
P7.20
230V: 350.0~450.0 VDC
390.0
460V: 700.0~900.0 VDC
780.0
0: Enable start-up lockout
16
P7.21
0
1: Disable start-up lockout
0: Always ON
17
P7.22
1: Fan OFF 1 minute after Stop
2: Run fan ON/Stop fan OFF
0
3: Heat sink temperature
18
P7.25
4: Always OFF
0~100%
60
19
P7.26
0: Warn and continue to operate
1: Warn and ramp to stop
3
20
P8.00
2: Warn and coast to stop
3: No warning
0.000~65.535 sec
0.500
21
P8.01
0.00~100.00% (of max current)
1.00
0: Warn and ramp to stop
0
1: Warn and coast to stop
22
P8.02
0.00~600.00 sec
0.20
230V models: 0.0~160.0 VDC
30.0
460V models: 0.0~320.0 VDC
60.0
23
P8.03
0.0~100.0%
60.0
0.00~655.35
0.10
0: STO Alarm Latch
24
P8.04
0
1: STO Alarm no Latch
♦ The diamond bullet symbol indicates a parameter that can be set during operation.
DURA
GS4 AC Drive Quick-Start Guide – 1st Ed, Rev.C 07/02/2021
pulse
DURA
GS4 Quick-Start Parameter Settings #5 – PID
pulse
Description
Settings
0: PID Disabled
1: PID Reverse Local/Remote
2: PID Forward Local/Remote
PID Action/Mode
3: PID Reverse Remote Only
4: PID Forward Remote Only
5: PID Reverse Local Only
6: PID Forward Local Only
1st Source of Frequency Command
0: Digital Keypad
[Remote]
1: RS485 Communication (Modbus/BACnet)
2: Analog Input
3: External UP/DOWN Terminal
2nd Source of Frequency Command [Local]
4: Comm Card
Analog Input 1 (AI1) Function
see
Analog Input 2 (AI2) Function
"Analog Input Settings" table
(page
Analog Input 3 (AI3) Function
AI1 – I/V Selection
0: AI_v Selection (0~10V)
1: AI_i Selection (4~20mA)
AI2 – I/V Selection
2: AI_i Selection (0~20mA)
PID Feedback Gain
0.00 to 300.00%
PID Offset Value
-100.0% to +100.0%
Proportional Gain
0.0~100.0
Integral Time
0.00~100.00 sec
Derivative Value
0.00~1.00 sec
PID Output Frequency Limit
0.0~110.0%
Feedback Signal Detection Time
0.0~3600.0 sec
0: Warn and Continue Operation
1: Warn and Ramp to Stop
PID Feedback Loss
2: Warn and Coast to Stop
3: Warn and Operate at Last Frequency
PID Feedback Loss Speed Level Default
0.00~400.00 Hz
0: Old PID mode, Kp, Kp*Ki, Kp*Kd
PID Mode Selection
1: New PID mode, Kp, Ki, Kd are
independent
0: PID can't change command direction
PID Reverse Enable
1: PID can change command direction
see
User Display
"User Display Settings" table
(page
0: Freq Setpoint
1: Output Hz
Start-up Display Selection
2: User Display (P8.00)
3: Output Amps
see
User Defined Format
"User Defined Format" table
(page
0: Disable
0~65535 (when P8.02 set to no decimal place)
User Defined Max
0.0~6553.5 (when P8.02 set to 1 decimal place)
0.00~655.35 (when P8.02 set to 2 decimal place)
0.000~65.535 (when P8.02 set to 3 decimal place)
User Defined Setpoint
0~65535
Default User
0
2
0
1
0
5)
0
0
1
100.00
0.0
1.0
1.00
0.00
100.0
0.0
0
0.00
0
0
5)
5)
0
0
Page 4