Dynalite DMC810GL Installatiehandleiding - Pagina 2
Blader online of download pdf Installatiehandleiding voor {categorie_naam} Dynalite DMC810GL. Dynalite DMC810GL 12 pagina's. Leading edge dimmer/hf ballast controller
Warning
TO REDUCE THE RISK OF FIRE OR
ELECTRIC SHOCK, DO NOT EXPOSE
THIS DEVICE TO RAIN OR MOISTURE.
DO
NOT
ENERGISE
FRONT COVER IS IN PLACE.
THIS DEVICE MUST BE EARTHED.
INSTALLATION,
MAINTENANCE MUST BE CARRIED OUT
BY QUALIFIED PERSONNEL
features
...................................................
Single Phase Supply
Simple supply requirement, single phase at 40A.
4 Dimmed Outputs
Each dimmed 10A output is independently
regulated, protecting loads from voltage surges
and spikes. These outputs are overload protected
by a single 10A circuit breaker shared with a
switched output.
4 Switched Outputs
Each switched output is rated at 10A. These
outputs are overload protected by a single 10A
circuit breaker shared with a dimmed output.
4 Control Outputs
Each of the 4 optically isolated outputs can be
configured to be either DALI Broadcast, 1-10V, or
DSI control, covering the latest types of HF
Fluorescent Ballasts and dimmable electronic
transformers. These outputs can operate in
tandem or independently of the switched outputs.
Convection Cooled
This device is naturally aspirated, requiring no
mechanical cooling system when installed in
accordance with these instructions.
Many Control Options
Control of this device can be from a combination
of available methods, eg. serial control port, relay
contacts, push button wall stations, infra red
receivers and timeclocks. Easy high level
interface to other popular AV control systems and
Building Management Systems (BMS) is also
available.
Simple Installation
Wall mount enclosure
facilitate
installation.
provided, at the top & side of the enclosure for
supply and load cables, with safety extra low
voltage (SELV) control section at the bottom.
.........................................................................................................................
UNLESS
THE
PROGRAMMING
AND
with mounting lugs
Cable
knockouts
are
important safeguards
.........................................................
Instructions – We recommend that you read this
Manual prior to installation, retain it and give the
end user.
Troubleshooting - If problems are encountered,
check the "Troubleshooting" section on page 10.
Special Programming – This device will only
operate in basic modes unless programmed via a
computer
or
a
portable
programming is required, contact your local agent
for details. Once the data cable is connected to the
devices, the factory default settings will allow any
control panel to control all channels in all dimmers.
Check Connections – Treat this device as a
switchboard that has been shipped. Tighten all
load-carrying screw connections, as vibrations from
transport can cause MCB and terminal block
screws to become loose.
Power Sources – This device should only be
operated from the type of supply specified on the
front panel. This device must be earthed.
Dimmed and Switched Output Circuits – The
load on a circuit should not exceed the specified
capacity of 10A for a dimmed channel and 10A for
a switched channel. Loads should be calculated to
ensure that the overall maximum capacity of 40A
(10A per pair of dimmed & switched channels) is
not exceeded.
Ballast Control Load Control Circuits – If this
device is being used to control DALI, 1-10V or DSI
HF Fluorescent Ballasts, a 2 core LV insulated
control cable is required to be run to the loads, in
addition to the mains feed. Note that the ballast
control outputs are not SELV as they are not double
insulated from mains.
Load Type – Default is for ballast load control
outputs to be 1-10V. Check to see what type of HF
Fluorescent Ballasts are in the luminaries. When
connecting 1-10V load control lines, pay attention
that the correct polarity is maintained.
Mounting Location – Device must be mounted
right way up, on a vertical surface (refer to page 4
for mounting instructions). The specified minimum
clearance of 100mm for all sides must be adhered
to.
Install in a dry, well-ventilated location.
Controllers may emit some mechanical noise. Take
this into account when deciding the mounting
location.
Data Cable – The recommended cable for
connections to the serial port is screened, stranded
RS485 data cable with three twisted pairs. Part
numbers for various manufacturers are listed on
page 6. This cable should be segregated from
mains cables by a minimum distance of 300mm –
subject to local wiring regulations. If anticipated
cable runs are over 600 metres for serial cables,
consult your dealer for advice. Do not cut or
terminate live data cables.
DMC810GL Instruction Manual Rev B.DOC
programmer.
If
2