5.0 TROUBLESHOOTING

Problem: Blank Display on the AirCycler®
Solution Check:
1. Confirm that the furnace has power.
2. Verify that the thermostat is operational.
3. Check that furnace will call for heat from the thermostat.
4. Ensure that fan operates with a fan-only signal from the thermostat
5. Confirm the furnace is providing a 24 VAC signal to the AirCycler®.
6. Verify that wiring conforms to wiring diagram.
7. Make sure top is firmly seated in the base.
Problem: AirCycler® FR-V turns furnace fan on and off, but the motorized damper does not cycle.
Solution Check:
1. Confirm that the AirCycler® is providing a 24 VAC signal to the motorized damper.
2. Verify that 24 VAC motorized damper is operational by powering directly with a 24 VAC signal.
3. Check continuity in the wiring between the damper and the AirCycler®.
Problem: A/C turns on during fan cycling calls
Solution Check:
1. Verify that wiring conforms to wiring diagram.
2. Ensure that the G wire is properly connected.
3. The G wire needs to be interrupted by the AirCycler®.
Do not run the G wire parallel.

Technical Support:

1.877.FAN.CONTrol